Manual
ibaBM-PN
44
Issue 1.9
Figure 26: „TAP“ node Device status and configuration
Application relations (AR)
Displays the current values
A tab is displayed per detected application relation, this appears when e.g. „shared
devices“ is used.
Status, controller MAC, type, creation time
Displays the current values
Communication relations (CR)
Displays the used Frame ID, cycle counter, data status, transfer status, data length,
cycle time and timeout for both communication directions.
Slots
Displays the configured subslots with subslot number, type, module ID, input length
and output length.
Hex viewer
Display of the binary data of the selected subslot.