background image

 

ESD GROUNDING:

 

HWR-014

 

ESD Hardware Kit

 

ESD  refers  to  the  OPTIONAL  static  dissipative  laminate  used  on  the  bench.  The  laminate  has  a 
conductive  under  layer  that  comes  in  contact  with  the  factory  installed  grounding  bolts  in  the 
worksurface.  The  ESD  grounding  kit,  including  the  10  ft.  grounding  wire must be attached and the 
bench  must  be  properly  grounded  to  your  facility  earth  ground.

  (See  below  for  grounding 

cautions!)

 The eyelet slips over the bolt end and the alligator clip attaches to ground. When tested 

with  a  megohmmeter  the  ground  bolts  should  test  at  1  (1x10

6

) to 1000 (1x10

9

) in accordance with 

EOS/ESD  standards  prescribed  in  EOS/ESD  document  S4.1-1990  Worksurfaces-Resistive 
Characterization. For specific details on grounding the bench consult EOS/ESD document S6.1-1991 
Grounding - Recommended Practice. 

 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

GROUNDING CAUTIONS: 

 

1.) Ground each bench individually to ground, 

NEVER t

o each other in a continuous daisy chain.  

2.) ISOLATED ground receptacles should not be used to derive an ESD ground.  
3.)  The  green  wire  in  a  standard  wall  duplex  can  be  used  as  a  ground  if  it  has  been  absolutely            
   determined that the green wire is attached to earth ground in your facility, thereby providing a real   
       earth ground.  
4.) Each component of an ESD station should be connected to the same common ground point. In 
other  words,  use  only  ONE  of  the  ground  bolts  as  a  path  to  ground.  There  are  2  installed  for 
convenience only, or in the event you purchase a continuous resistance monitor.  