shall be no less than 1
x
10
3
Ω
. Measure temperature
gage resistance – the value shall correspond to the
stated in the thermostat certificate value.
J
Shortly (for 1–2 minutes) apply voltage and check
for integrity of the system (a LED on the face panel
of the thermostat shall light). Turn off the power
again and do not turn it on until the system is put
into service.
J
Mark the thermostat, service box, temperature
gage and heating section locations on the room
plan, as well as the make of the heating section and
measured heating section and temperature gage
resistance values.
J
Cover the floor with 3–5 cm mortar (5 cm, min., in
case of main heating).
J
Let the solution dry according to its application
instructions.
J
After the solution has dried up, check for damages
of the heating section and temperature gage
according to the recommendations above.
J
Finish with ceramic tiles or apply any other decora
tive finishing.