Table 1
The heating system shall be connected via a RCD
(residual current device) with nominal operative current
below 30 mA. This is a small device, which is mounted in
an electric board, to monitor electric insulation of your
equipment. If the floor heating system is to be installed in
wet premises (bathrooms, saunas, swimming pools), the
shield of the heating section shall be connected to the
supply main grounding conductor, which, in turn, shall be
connected with all the metal elements, such as: metal
shower trays, metal shower cabin frames and so on.
Choose the thermostat location. It shall be convenient
ly wallmounted not impeding placement of furniture.
Thermostats for heating systems in wet rooms
(bathrooms, toilets, saunas, swimming pools) shall
be located outside these rooms.
Conductor
material
Section,
mm
2
Max. load
current, A
Max. total heating
power, kW
Copper
2
х
1,0
16
3,5
2
х
1,5
19
4,1
2
х
2,5
27
5,9
Aluminium
2
х
2,5
20
4,4
2
х
4,0
28
6,1
www.iwarm.com
Spooled Underfloor Heating Kit
11