TABLE 4 :

 Below listed points will appear only if O/P2 is selected as an Alarm mode. In Alarm mode, Controller 

continuously compares PV with either SP (for deviation or Band -alarm) or an independent Alarm set points (for 
process high and process low alarm). HYS2 in Control list decides when to switch OFF the Alarm. 

7

OIM AI-7X82 V2.0 Page 7 of 9

Low Alarm : OP2 activates when PV<SP2.

OUTPUT-2 ON

OUTPUT-2 OFF

SP2

PV

SP2

OUTPUT-2 OFF

OUTPUT-2 ON

PV

High Alarm : OP2 activates when PV>SP2.

OUTPUT-2 OFF

OUTPUT-2 ON

SP2

PV

Direct acting

SP2

OUTPUT-2 ON

OUTPUT-2 OFF

PV

Reverse acting

DEVIATION

Band Alarm : OP2 activates when PV falls outside the band w.r.t. SP1 in either 
direction.

OUTPUT ON

OUTPUT ON

PV

SP1

SP2

SP2

OUTPUT OFF

OUTPUT OFF

OUTPUT OFF

PV

SP1

SP2

SP2

OUTPUT ON

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

DEFAULT

DESCRIPTION

ALARM

TYPE

ALARM

LOGIC

DIRECT

User can select direct Alarm Logic in which OP2 will be ON under alarm condition; 
otherwise OFF (used for audio visual alarm).   

User  can  select  Reverse  Alarm  Logic  in  which  OP2  will  be  ON  in  normal 
conditions & will be OFF under alarm conditions (used to trip the process in alarm 
conditions).

ALARM
INHIBIT

If  this  parameter  is  set  as  ‘YES’  & Alarm  condition  persists,  it  will  Disable Alarm 
O/P at power ON.

If this parameter is set as ‘NO’ & Alarm condition persists, it will Enable Alarm O/P 
at power up.

NO

ALARM

ACK.

AUTO

Once the Alarm is activated, User has following three options to de-activate it.
When PV falls within  the programmed limits The Alarm will be de-activated 
automatically.

Once the alarm is activated, it remains activated until acknowledged manually by  
UP key.

Once the alarm is activated, it can be de-activated either by pressing UP key  or 
when PV falls within the alarm limits.

ALARM

SET

POINT

Enable

If Enabled, User can View & edit the Alarm Set point in USER list. 

If disabled, User can not View or edit Alarm Set Point in USER list.

High Deviation Alarm : OP2 activates when PV is greater than SP1 ± set 
deviation value

OUTPUT ON

PV

SP1

OUTPUT OFF

OUTPUT OFF

+Ve
 dev

PV

Sp1

OUTPUT ON

Low Deviation Alarm : OP2 activates when PV is less than SP1 ± set deviation 
value

OUTPUT OFF

PV

OUTPUT ON

OUTPUT ON

PV

OUTPUT OFF

SP2

SP2

SP2

SP2

OUTPUT ON

PV

SP1

OUTPUT OFF

OUTPUT ON

PV

OUTPUT OFF

SP2

SP2

OUTPUT OFF

PV

SP1

OUTPUT ON

OUTPUT OFF

PV

OUTPUT ON

SP2

SP2

-Ve

 dev

+Ve
 dev

+Ve
 dev

+Ve
 dev

-Ve

 dev

-Ve

 dev

-Ve

 dev

Summary of Contents for AI-7482

Page 1: ...bon dust salt air direct sunlight or radiant heat v Ambient temperature and relative humidity surrounding the controller must not exceed the maximum specified limit for proper operation of the controller v The controller in its installed state must be protected against excessive electrostatic or electromagnetic interferences Ventilation holes provided on the chassis of the instrument are meant for...

Page 2: ...782 AI 7982 FRONT PANEL LAYOUT AI 7882 AI 7682 Glows when OP1 is ON flashes when delay time dly1 is in operation if selected mode is ON OFF Glows when OP2 is ON flashes when alarm condition persists even after acknowledged OR delay time dly2 is in operation selected mode is ON OFF Glows when Soak mode is selected flashes when Soak timer is in operation along with UP key 4 To scroll the parameter t...

Page 3: ...upon the error SV PV Value of this parameter is automatically set by Auto tune function o 5 0 C LOWER DISPLAY UPPER DISPLAY PARA METER RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters OUTPUT OFF 1 to10 This parameter will be prompted only if selected control action is PID With this parameter ...

Page 4: ...ered at every power ON This parameter will be prompted only if selected control mode for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously ON at the end of Soak time till User starts the next cycle This parameter defines the permissible deviation of PV f...

Page 5: ...ID User can select between PID or ON OFF action algorithm to be adopted for output HEAT CONTROL LOGIC FOR O P 1 User can select heating logic in which OP1 will remain ON till PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD or RTD 1 and is used for B...

Page 6: ...list OUTPUT 2 CONTROL 15 0 This parameter will appear only if Control logic is Heat Cool OP2 will be OFF at Ambient OP2C value irrespective of output 2 mode Auxiliary Toggle OUTPUT 2 FUNCTION This parameter allows the user to select output 2 as an Auxiliary control For options refer Table 3 This parameter allows the user to select output 2 as an Alarm control For options refer Table 4 This paramet...

Page 7: ...der alarm conditions used to trip the process in alarm conditions ALARM INHIBIT If this parameter is set as YES Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up NO ALARM ACK AUTO Once the Alarm is activated User has following three options to de activate it When PV falls within the programmed...

Page 8: ... only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress TIMER START MODE MOD 2 In this Mode Timer will start only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle After executin...

Page 9: ... undershoot Auto tuning is applied in case of 1 Initial set up for a new process 2 Substantial change in SP from previous auto tuning value 3 Control accuracy is not satisfactory If the control performance by using auto tuning is still unsatisfactory User can apply further adjustments of P I D values as shown in Table 3 below Fig 3 1 HEAT LOGIC ON OFF TIME 0 TEMP C HYSTERISIS SP ON ON ON AMB O P O...

Reviews: