Note : -

 1) User can restart soak time at any moment during its execution, by pressing START key for 3 sec.

TABLE 5 :

 Below listed option will appear only if OP2 is selected as a soak timer. 

8

OIM AI-7X82 V2.0 Page 8 of 9

If set as ‘YES’, soak time value will not be stored at the time of power failure. 

If set as ‘NO’ at power ON, soak time will continue from stored value. 
(Note: Seconds will not be stored.)

RESET

OF 

RUNNING 

SOAK

TIME

 NO

If selected, soak timer will  increment (from 0 to set value)
(Note:- User can alter the new time value which should be > elapsed  time even if 
soak timer is running. If user sets new time value < elapsed  time, running timer 
will be terminated & End of soak Strategy will be executed.

If selected ,soak timer will decrement (from set value to 0).
(Note:- User can alter the new time value  even when soak timer is running. In this 
case,  balance  time  of  previous  set  value  will  be  ignored  &  new  cycle  will  be 
executed.

DIRECTION

FOR 

SOAK

TIME

 DN

User can define 4 different modes to start the soak timer as follows : - 
In this mode, Timer will start after pressing START key for 3 sec.,  irrespective of 
PV.

In this Mode, after power ON Timer starts when PV >= SV. To continue with next 
cycle, user has to either switch Power on & off 

OR

 press START key for 3 sec 

when STRT message is displayed on the lower display.

In this Mode, Timer will start only after pressing START key for 3 sec & PV>=SV 
for any of  the following conditions.
(1) At every Power ON. 
(2) Completion of current soak time cycle.  
(3) Power failure during soak time is in progress.

TIMER

START

MODE

 MOD 2

In this Mode, Timer will start only after pressing START key for 3 sec & PV>=SV 
for any of  the following conditions.
(1) At every Power ON. 
(2) Completion of current soak time cycle. 
After executing start command, if cycle doesn't complete due to power failure, 
cycle will continue whenever PV >= SV after restore of power. 

No need to press 

START key.

LOWER

DISPLAY

UPPER

DISPLAY

 PARA

METER

DEFAULT

DESCRIPTION

END OF

SOAK

STRATEGY

It defines the behaviour of the controller at the end of soak timer cycle .  Options 
are as below. If  selected, the controller maintain PV at SP indefinitely irrespective 
of start or end of a soak timer. 

The controller de-energizes OP1 as soon as the soak time is over. Here upper 
display will continue to show PV & lower display will show message "start".Next 
cycle will start only when user press START key for 3 sec.

The controller energizes OP2 for a time period programmed via (StdL) parameter 
at the end of a soak time cycle. User can utilise OP2 for audio/visual indication.

The controller executes both, the Heater OFF and Alarm ON function as 
described above.

BOTH

User can select the timer base of soak time among the four options as shown.
Minutes & Seconds (Range 99 minutes, 59 seconds).

Minutes (Range 9999 minutes).

Hours & Minutes (Range 99 Hours , 59 minutes).

Hours (Range 999.9 Hours).

TIME

BASE

SOAK

TIMER

 MMMM

Summary of Contents for AI-7482

Page 1: ...bon dust salt air direct sunlight or radiant heat v Ambient temperature and relative humidity surrounding the controller must not exceed the maximum specified limit for proper operation of the controller v The controller in its installed state must be protected against excessive electrostatic or electromagnetic interferences Ventilation holes provided on the chassis of the instrument are meant for...

Page 2: ...782 AI 7982 FRONT PANEL LAYOUT AI 7882 AI 7682 Glows when OP1 is ON flashes when delay time dly1 is in operation if selected mode is ON OFF Glows when OP2 is ON flashes when alarm condition persists even after acknowledged OR delay time dly2 is in operation selected mode is ON OFF Glows when Soak mode is selected flashes when Soak timer is in operation along with UP key 4 To scroll the parameter t...

Page 3: ...upon the error SV PV Value of this parameter is automatically set by Auto tune function o 5 0 C LOWER DISPLAY UPPER DISPLAY PARA METER RANGE DESCRIPTION DEFAULT CONTROL LIST SET DOWN key simultaneously To enter in this mode press for 3 sec User can then set the following control parameters OUTPUT OFF 1 to10 This parameter will be prompted only if selected control action is PID With this parameter ...

Page 4: ...ered at every power ON This parameter will be prompted only if selected control mode for Output2 is Soak timer Depending on end of soak strategy the value of this parameter sets the activation time for OP2 when Soak timer is over Setting this parameter to 0 will make OP2 continuously ON at the end of Soak time till User starts the next cycle This parameter defines the permissible deviation of PV f...

Page 5: ...ID User can select between PID or ON OFF action algorithm to be adopted for output HEAT CONTROL LOGIC FOR O P 1 User can select heating logic in which OP1 will remain ON till PV SP PV increases when output is ON User can select cooling logic in which OP1 will remain ON till PV SP PV decreases when output is ON This parameter will be prompted only if selected input is RTD or RTD 1 and is used for B...

Page 6: ...list OUTPUT 2 CONTROL 15 0 This parameter will appear only if Control logic is Heat Cool OP2 will be OFF at Ambient OP2C value irrespective of output 2 mode Auxiliary Toggle OUTPUT 2 FUNCTION This parameter allows the user to select output 2 as an Auxiliary control For options refer Table 3 This parameter allows the user to select output 2 as an Alarm control For options refer Table 4 This paramet...

Page 7: ...der alarm conditions used to trip the process in alarm conditions ALARM INHIBIT If this parameter is set as YES Alarm condition persists it will Disable Alarm O P at power ON If this parameter is set as NO Alarm condition persists it will Enable Alarm O P at power up NO ALARM ACK AUTO Once the Alarm is activated User has following three options to de activate it When PV falls within the programmed...

Page 8: ... only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle 3 Power failure during soak time is in progress TIMER START MODE MOD 2 In this Mode Timer will start only after pressing START key for 3 sec PV SV for any of the following conditions 1 At every Power ON 2 Completion of current soak time cycle After executin...

Page 9: ... undershoot Auto tuning is applied in case of 1 Initial set up for a new process 2 Substantial change in SP from previous auto tuning value 3 Control accuracy is not satisfactory If the control performance by using auto tuning is still unsatisfactory User can apply further adjustments of P I D values as shown in Table 3 below Fig 3 1 HEAT LOGIC ON OFF TIME 0 TEMP C HYSTERISIS SP ON ON ON AMB O P O...

Reviews: