i
Note : -
1) User can restart soak time at any moment during its execution, by pressing START key for 3 sec.
TABLE 5 :
Below listed option will appear only if OP2 is selected as a soak timer.
8
OIM AI-7X82 V2.0 Page 8 of 9
If set as ‘YES’, soak time value will not be stored at the time of power failure.
If set as ‘NO’ at power ON, soak time will continue from stored value.
(Note: Seconds will not be stored.)
RESET
OF
RUNNING
SOAK
TIME
NO
If selected, soak timer will increment (from 0 to set value)
(Note:- User can alter the new time value which should be > elapsed time even if
soak timer is running. If user sets new time value < elapsed time, running timer
will be terminated & End of soak Strategy will be executed.
If selected ,soak timer will decrement (from set value to 0).
(Note:- User can alter the new time value even when soak timer is running. In this
case, balance time of previous set value will be ignored & new cycle will be
executed.
DIRECTION
FOR
SOAK
TIME
DN
User can define 4 different modes to start the soak timer as follows : -
In this mode, Timer will start after pressing START key for 3 sec., irrespective of
PV.
In this Mode, after power ON Timer starts when PV >= SV. To continue with next
cycle, user has to either switch Power on & off
OR
press START key for 3 sec
when STRT message is displayed on the lower display.
In this Mode, Timer will start only after pressing START key for 3 sec & PV>=SV
for any of the following conditions.
(1) At every Power ON.
(2) Completion of current soak time cycle.
(3) Power failure during soak time is in progress.
TIMER
START
MODE
MOD 2
In this Mode, Timer will start only after pressing START key for 3 sec & PV>=SV
for any of the following conditions.
(1) At every Power ON.
(2) Completion of current soak time cycle.
After executing start command, if cycle doesn't complete due to power failure,
cycle will continue whenever PV >= SV after restore of power.
No need to press
START key.
LOWER
DISPLAY
UPPER
DISPLAY
PARA
METER
DEFAULT
DESCRIPTION
END OF
SOAK
STRATEGY
It defines the behaviour of the controller at the end of soak timer cycle . Options
are as below. If selected, the controller maintain PV at SP indefinitely irrespective
of start or end of a soak timer.
The controller de-energizes OP1 as soon as the soak time is over. Here upper
display will continue to show PV & lower display will show message "start".Next
cycle will start only when user press START key for 3 sec.
The controller energizes OP2 for a time period programmed via (StdL) parameter
at the end of a soak time cycle. User can utilise OP2 for audio/visual indication.
The controller executes both, the Heater OFF and Alarm ON function as
described above.
BOTH
User can select the timer base of soak time among the four options as shown.
Minutes & Seconds (Range 99 minutes, 59 seconds).
Minutes (Range 9999 minutes).
Hours & Minutes (Range 99 Hours , 59 minutes).
Hours (Range 999.9 Hours).
TIME
BASE
SOAK
TIMER
MMMM