2-2
CMS-6R4 Series - User’s Guide
2.2. Back Panel Components
Power Inlet and Circuit Breaker:
An AC inlet and circuit breaker
which supply power to the CMS-6R4. Includes cable keeper (not shown.)
•
Model CMS-6R4 (120 VAC):
IEC-320-C14, 100 - 120 VAC Power
Inlet, 15 Amp Circuit Breaker.
•
Model CMS-6R4-CE (230 VAC):
IEC-320-C14, 208 - 240 VAC
Power Inlet, 10 Amp Circuit Breaker.
Switched Plugs and Plug Indicators:
Four AC Outlets that can be
switched On, Off, Rebooted or set to user-defined Default values in
response to user commands.
•
Model CMS-6R4:
Four 100-120 VAC, NEMA 5-15 Outlets with
indicator lights. 15 Amps Total Load.
•
Model CMS-6R4-CE:
Four 208-240 VAC, IEC-320-C13 Outlets with
indicator lights. 10 Amps Total Load.
Serial RS232 Ports:
For connection to console ports on target devices.
Standard DB9 connectors configured as DTE ports, similar to a serial port
on a PC. When connecting a modem, use a standard serial cable. When
connecting a PC or other DTE device use a null modem cable.
Notes:
• Ports 1 is a System Setup Port. In order to ensure local access by
system administrators, Supervisor Level command capability cannot
be disabled at Port 1, and the Port Mode cannot be set to "Buffer" or
"Passive".
• Port 2 can also be used as a Setup Port, providing that the Port Mode
is set to Any-to-Any and the Supervisor Mode is enabled.
O
I
PHONE LINE
10BaseT
ACT
SYSTEM
SETUP
PORTS
15 AMPS
MAX
PLUG 1
PLUG 2
PLUG 3
PLUG 4
2
1
3
4
5
6
1
2
3
4
5
6
Figure 2.2: Back Panel Components (120 VAC Model Shown)