Inverter RS485 Interface Instruction Manual
(4) Data value setting [Note 2]
Data value is transmitted except decimal point.
Ex1) Output frequency
Parameter value
Communication data
Converted hexadecimal value
60.00Hz
6000
1st byte : 0x17
2nd byte : 0x70
Ex 2) acceleration/deceleration time
Parameter value
Communication data
Converted hexadecimal value
10.0sec
100
1st byte : 0x00
2nd byte : 0x64
(5) Special parameter [Note 3]
A special parameter is used to operating and commanding a frequency value for the
basic parameter.
①
Run command Parameter
1st byte : 0x00
2nd byte : 0x02
Setting data
1st byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
2
nd
byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Reserved
RST
REV
FWD
Data value on RUN command
1
st
Byte
2
nd
Byte
Byte & Bit
Command
7
6
5
4
3
2
1
0
7
6 5 4 3 2
1
0
Forward RUN (0x01)
0
0
0
0
0
0
0
0
0
0 0 0 0 0
0
1
Reverse RUN (0x02)
0
0
0
0
0
0
0
0
0
0 0 0 0 0
1
0
STOP (0x00)
0
0
0
0
0
0
0
0
0
0 0 0 0 0
0
0
N100_Inverter RS485 Interface Manual(English).doc