N100
plus
Inverter RS485 Interface Instruction Manual
2.2
Setting Request & Response Data
2.2.1
A prior condition
(1) Communication number :
01
(Inverter address 1)
(2) Command
:
06 (Setting
request)
2.2.2
Output frequency setting (Function code : F01)
Please refer to
Clause 2.3 Frequency command on page 13
.
2.2.3
Example 4 – Acceleration time 1 setting (F02)
(1) Transmit Data (In case of 10sec)
Transmit (8Byte)
Com.
Num.
Com-
mand
Parameter
Data
CRC 16
Hi Lo
0106020200642859
01 06 02 02 00
64 28 59
Data Description
0x16
3
+ 0x16
2
+ 6x16
1
+ 4x16
0
= 100 (Communication Data)
Î
divide by 10
Î
10.0sec (Parameter value)
(2) Response
Data
Response (8Byte)
Com.
Num.
Com-
mand
Parameter
Data
CRC 16
Hi Lo
0106020200642859
01 06 02 02 00
64 28 59
2.2.4
Example 5 – Deceleration time 1 setting (F03)
(1) Transmit Data (In case of 30sec)
Transmit (8Byte)
Com.
Num.
Com-
mand
Parameter
Data
CRC 16
Hi Lo
01060203012C783F
01 06 02 03 01
2C 78 3F
Data Description
0x16
3
+ 1x16
2
+ 2x16
1
+ 12x16
0
= 300 (Communication Data)
Î
divide by 10
Î
30.0sec (Parameter value)
(2) Response
Data
Response (8Byte)
Com.
Num.
Com-
mand
Parameter
Data
CRC 16
Hi Lo
01060203012C783F
01 06 02 03 01
2C 78 3F
N100_Inverter RS485 Interface Manual(English).doc
13