S826/6 

POWER STATUS

 

MAINS VERSION: The Power LED will remain illuminated to indicate that 
there is mains power to the unit 

 

BATTERY  VERSION:  The  Battery  LED  will  flash  every  2  seconds  to 
indicate  that  there  is  battery  power  to  the  unit.  If  the  battery  charge  is  too 
low then the sounder will activate intermittently to indicate this. 

 

ALARM CONDITION 

 

When a high or low-level alarm condition occurs the corresponding channel 
LED  on  the  tank  alarm  lid  is  illuminated  and  the  sounder/beacon  will 
activate. The external relay will also be activated.  
 

FLOAT SWITCH FAULT INDICATION

 

If  any  of  the  channel  LEDs  flashes  repeatedly  then  this  indicates  a  fault 
with the float switch. 
 

ALARM MUTE 

 

Pressing the mute button for 1.5 seconds will silence the sounder and stop 
the beacon flashing when an alarm condition is occurring. This will not de-
activate any relays (if fitted). The relays will only be de-activated when float 
switch returns to its normal position.  

If  the  mute  button  is  not  depressed  the  sounder  will  silence  after  20 
minutes leaving the beacon and channel LED on.  

 

The channel LED will remain on until the alarm condition has been rectified 
(float switch returns to its normal position).

 

 

  ALARM TEST

 

 

To test the Tank Alarm, push and hold the test button on the lid. If the Tank 
Alarm  is  functioning  correctly  the  sounder  should  activate,  the  beacon  will 
flash (if fitted) and all activated channel LEDs will illuminate.  
If  any  of  the  channel  LEDs  flashes  repeatedly  then  this  indicates  a  fault 
with the float switch. 

 

Battery version:

 If no sounder is heard and  no  channel LED’s illuminate, 

check batteries and change as necessary.  

 

NB: Always push the Tank Alarm test button before filling the tank. 
 

 

Summary of Contents for TA3A.B

Page 1: ...P TA3A PR TA3A B TA3A BR Please read carefully before commencing installation Registered Office HYTEK GB LIMITED Delta House Green Street Elsenham Bishop s Stortford CM22 6DS UK Registered in England No 1915382 Tel 44 0 1279 815 600 Fax 44 0 1279 812 978 email info hytekgb com Web www hytekgb com ...

Page 2: ...ches and an enclosure weatherproof to an IP54 standard which contains the visual and audible alarms and the electronic PCB This alarm is approved to operate with flammable liquids classed as category 1 2 or 3 in accordance with European Regulation No 1272 2008 It is ATEX certified in accordance with EN 60079 0 2012 and EN 60079 11 2012 It is also IECEx certified in accordance with IEC 60079 0 2011...

Page 3: ...y alkaline batteries of the same make shall be used as replacements All batteries shall be replaced at the same time IMPORTANT WARNING NOTES 1 This alarm is designed for use with liquids classed as category 1 2 or 3 in accordance with European Regulation No 1272 2008 including petrol diesel gas oil water hydraulic oil and heating oil It can be used with Anti freeze or Adblue if the optional stainl...

Page 4: ...button checks float switches as well as beacon sounder BATTERY VERSION Battery 3 channel alarm Each channel can be used as an overfill low level or bund alarm High power alarm sounder No zenon beacon but individual channel LED s Test button checks float switches as well as batteries sounder Battery life depends on number of test alarm incidents INSTALLATION INSTRUCTIONS MOUNTING The float switch a...

Page 5: ...ate the gland fitted to the gland plate at the appropriate point along the float switch cable Carefully install float switch through a 30mm hole in the top of the tank ensuring the sealing gasket is in place Secure the gland plate to the tank using two self tapping screws not supplied See Float switch installation diagram page 3 Alternatively for steel tank installations an optional 11 2 brass cap...

Page 6: ...ng the appropriate channel activation dipswitch to ON position See Dip switch settings diagram NB If a channel activation dipswitch is in the OFF position and a float switch connected to the corresponding terminals is operated the alarm will not function 8 Set the high low level dipswitches to the appropriate position NORM high level activation INVERT low level activation to enable the correspondi...

Page 7: ...y and do not offer a power source for any external equipment The relays MUST NOT be used to activate any equipment such as fuel pumps or safety valves COMPLETION OF INSTALLATION 10 Install batteries provided TA3A B TA3A BR Only 11 Refit lid to alarm box ensuring that ribbon cable is reconnected to the main PCB and the lid seal is in place 12 Switch on power The green POWER LED should illuminate TA...

Page 8: ...under and stop the beacon flashing when an alarm condition is occurring This will not de activate any relays if fitted The relays will only be de activated when float switch returns to its normal position If the mute button is not depressed the sounder will silence after 20 minutes leaving the beacon and channel LED on The channel LED will remain on until the alarm condition has been rectified flo...

Page 9: ...S826 6 FITTING DIMENSIONS ...

Page 10: ...rm PCB 230Vac with Relays TA3A PCBM Alarm PCB 230Vac TA3A PCBR Alarm PCB 6Vdc Battery with Relays TA3A PCBB Alarm PCB 6Vdc Battery 10 TA CONM Plug connector 230 110v mains 11 TA CONR Plug connector relays 12 TA CONF Plug connector floats 13 BLANK 12 7 12 7mm hole blank 14 TA LABP Product label 9 labels per sheet 15 TA PCBDISP Alarm display PCB not shown SPARES PART NUMBER DESCRIPTION TA FA5 5m uni...

Page 11: ...S826 6 OUTSIDE VIEW 2 4 5 6 8 1 3 TA3A P 230V AC SHOWN ...

Page 12: ...79 11 2011 Ed 6 EC Type examination Certificate No CML 16ATEX2355X IECEx CML 16 0128X Marking Alarm Box Float Sensor Notified Body CML Ltd Unit 1 Newport Business Park New Port Road Ellesmere Port CH65 4LZ UK Notified Body Number CML 2503 Declaration Number EU130 3 On behalf of the above named company I declare under our sole responsibility that on the date the equipment accompanied by this declar...

Reviews: