S826/6
POWER SUPPLY
4. The TA3A.P and TA3A.PR are designed to have a continual 230V AC
supply fused at a rating of 6 amps max. The TA3A.B and TA3A.BR
have an internal battery power supply. See Connections diagram.
CONNECTIONS DIAGRAM
FLOAT SWITCH INSTALLATION
5. To ensure the float switch is positioned at the correct depth in the tank,
locate the gland, fitted to the gland plate, at the appropriate point along
the float switch cable.
Carefully install float switch through a 30mm hole in the top of the tank,
ensuring the sealing gasket is in place. Secure the gland plate to the
tank using two self-tapping screws (not supplied). See Float switch
installation diagram (page 3). Alternatively, for steel tank installations,
an optional 11/2” brass cap (Hytek order ref - TA.CAP) can be used.
NB: Installation of the float switch should be as far away from the fill
point of the tank as possible
.