3-6
S
ETUP
Operator Manual
POWER CORD PLUGS
All 208/240/480V power supplies are shipped with a single-phase power cord and plug
. To operate
as a three-phase unit, the user must obtain a power cord and plug that is certified by national or local
electrical codes. The plug should be connected to the power cord by a licensed electrician.
All 200/230/400V and 400V CE power supplies are shipped with a three-phase power cord and no
plug
. The user must obtain a plug that is certified by national or local electrical codes. The plug should
be connected to the power cord by a licensed electrician.
POWER CORDS
If the power cord needs to be changed, use the tables below to choose the proper wire size for the
appropriate length cord. Note that the input current used to determine the cord size is I
1eff
. In the U.S.,
use a 3-conductor SO type cord for single-phase, and a 4-conductor SO type cord for three-phase power
supplies. In other countries, use cords that are certified by national or local codes. Prepare the power
cord wires as shown in Fig. 3-6 for non-CE power supplies, or Fig. 3-6a for CE power supplies. Note that
all 4 wires must loop through the toroid in the CE power supply. Cap or tin the conductor leads and use a
#10 terminal on the ground wire. The cord should be installed only by a licensed electrician.
208/240/480/600V Power Supplies
Input
Phase
Input
Recommended Power Cord Gauge Size (AWG)
Voltage
Current (I
1eff
)
< 10 ft
10 – 25 ft
25 – 50 ft
50 – 100 ft
100 – 150 ft
208 VAC
1
39A
8
8
6
4
4
240 VAC
1
33A
8
8
8
6
4
480 VAC
1
19A
12
12
12
10
8
208 VAC
3
23A
8
8
8
6
4
240 VAC
3
20A
10
10
10
8
6
480 VAC
3
10A
12
12
12
12
10
600 VAC
3
8A
12
12
12
12
10
Input
Phase
Input
Recommended Power Cord Gauge Size (mm
2
)
Voltage
Current (I
1eff
)
< 3 m
3 – 7.5 m
7.5 – 15 m
15 – 30 m
30 – 45 m
200 VAC
1
40A
10
10
16
25
25
230 VAC
1
35A
6
6
10
16
25
400 VAC
1
23A
4
4
4
6
10
200 VAC
3
23A
4
4
6
16
25
230 VAC
3
21A
2.5
4
6
10
16
400 VAC
3
13A
2.5
2.5
2.5
4
6
200/230/400V Power Supplies
4.5" (114 mm)
3.5" (89 mm)
Figure 3-6 Power Cord Preparation - Non-CE
L1
L2
L3
Ground
#10
Figure 3-6a Power Cord Preparation - CE
4.75" (120 mm)
3.75" (95 mm)
L1
L3
#10
L2
0.5" (13 mm)
Ground
All wires 1 turn
through toroid.
Summary of Contents for powermax900
Page 1: ......
Page 15: ...SAFETY 1 6 Hypertherm Plasma Systems 8 99 ...
Page 21: ...SÉCURITÉ 1a 6 08 99 HYPERTHERM Systèmes plasma ...
Page 50: ...OPERATION 4 9 Operator Manual Figure 4 8 Dragging the Torch Figure 4 7 Cutting a Circle ...
Page 69: ...Operator Manual 5 14 MAINTENANCE PARTS ...
Page 73: ...APPENDIX B Operator Manual ...