Page 24
7. Electrical connection
Danger of electrical shock!
Dangerous electrical voltage!
All work relating to the electrical installation
may only be carried out by designated spe-
cialist personnel (electrician or qualified per-
son with equivalent training).
Do not connect the steam humidifier to the
live power supply before all installation work
has been completed.
The customer is responsible for monitoring
the qualifications of the specialist personnel.
General installation rules
•
All local rules concerning the imple-
mentation of electrical installations
must be obeyed
•
Install the electrical connections accor-
ding to the wiring diagram
Possible electronical components de-
struction through electrostatical dis-
charge!
Prior to commencing electrical installation
work, steps must be taken to guard the sen-
sitive electronical components of the unit con-
trol against damage from electrostatical
discharge.
7.1 Electrical installation
approach
»
Provide fuses with a contact gap of
at least 3mm per pole.
»
Make main connection according to
the table below.
Main connections
Please refer to the table of technical data
(see chapter at the end of this manual) for the
connection values of the installation kits.
Fusing
HygroMatik recommends the use of slow
blowing up to middle time-lag main fuses
(only applies to the a.m. mains supply volt-
ages).
The kit installation should encorporate an
individual residual current device (Type A-
RCD).
Maximum current draw of the kit models and
the required fusing resulting from that can be
found in the technical data (see chapter at
the end of the manual).
WARNING
!
Please note
NOTICE
Please note