5.5 Unit Installation Check
Before start-up, pls. check proper unit instal-
lation following the list below:
Kit perpendicularly aligned in both
the vertical and horizontal axis ?
Steam hose installed with a 5 - 10 %
minimum incline/decline (see chap-
ter "Steam line“) ?
Condensate hose features a loop
functioning as a steam barrier (see
chapter „Condensate hose“) ?
Steam manifold(s) properly posi-
tioned?
All bolts and clamps properly tight-
ened?
Steam manifold(s) horizontally
mounted and suspended on the free
end, if required ?
All seals (o-rings) in place?