Page 63
r08 External demand
(only with ext. controller)
External controller control signal is displayed
[%]
r09 Power limitation
Power limitation as a percentage of max. output as preset in param-
eter „1-1“ is displayed
[%]
r10 Set point r.H.
(only
when PI controller was
preset)
R.h. nominal value as preset in parameter 4-1 is displayed
[%]
r11 Actual value r.h.
(only when PI controller
was preset)
Actual value of r.h. is displayed [%].
r12 External signal
External signal [%]
r13 V-Signal
Input signal measured at terminal ST805 [V]
r14 mA-Signal
Input signal measured at terminal ST806 [mA]
r15
Ω
-Signal
Input signal measured at terminal ST807 [
Ω
]
Set value
Explanation
P00 Code level
Allows provider level access by code input (Code „10“) or limitation
to user level (Code „0“). Provider level is exited automatically after
10 mins without a keystroke.
PAr Parameter selection
Allows selection of parameter group and of a specific parameter
within a group.
Reading value
Explanation