8.6 Cleaning the Blow- Down Pump
»
Remove cylinder, as described in Section: "Removing
and Cleaning the Steam Cylinder” .
»
Detach e-cable from the pump.
»
Detach adapter (30) from the pump.
»
Loosen screws (44) and remove the pump from the
base.
»
Open the pump (bayonet lock).
»
Remove residues from the drain hoses and pump
(potentially replace o-ring (33) or
housing (34) if these
components are no longer in excellent condition).
»
Reassemble the pump.
»
Moisten o-ring (31) and insert in the side connection of
the base.
»
Push pump into the base and mount tightly with screws
(44).
»
Moisten o-ring (31) and insert in adapter (30).
»
Fit adapter (30) over the side connection of the pump.
»
Connect e-cable to the pump.
» Inst
all cylinder,
»
Switch on the unit and check for leaks during operation.
If leakage occu rs, switch of f power su pply and follow safety
instructions for work on live components.
8.7 Cleaning the Water Inlet Solenoid Valve
Removal
»
Shut off water supply.
»
Remove cylinder, as described in Section: "Removing
and Cleaning the Steam Cylinder” .
»
Loosen water installation hose connection.
»
Loosen connecting hose (21) from the base.
»
Detach e-cable from the solenoid valve.
»
Loosen solenoid valve mounting screws (28).
»
Remove solenoid valve from the borehole.
»
Remove fine mesh filter (29) from the solenoid valve,
clean and replace if needed.
Installation
»
Insert fine mesh filter (29).
»
Place solenoid valve with seal in the borehole of the
Summary of Contents for MiniSteam MS 10
Page 1: ...Electrode Steam Humidifier MiniSteam MS ENU MS EN Manual...
Page 16: ...Page 16 5 1 1 Fitting measures Wall Distances mm 150...
Page 18: ...Page 18 5 3 Unit Dimensions Water inlet Waste water connection Cable entries...
Page 39: ...Page 39 10 EC Declaration of Conformity...
Page 45: ...Page 45 15 View of housing...
Page 46: ...12 2004...