Page 21
strainer must be placed inside the solenoid valve.
»
Use a cap nut (internal thread ¾“) with inner seal for a
customer-provided water installation.
6.3 Water discharge
Warning:
During blow down hot wat er wit h a temperature of
about 95°C is being drained. If touched this can cause burns to
the skin.
Warning:
Pay atte ntion for fre e and non- pressure d rainage of
the water! During blow down u p to 0,3 L/sec are being drained.
For water discharge, we recommend inst allation of a flexible
water drain hose. Humidifier and wastewater discharge must be
on the same pressure level.
Please note:
•
Do not bend the drain hose.
•
Install discharge line and drain pipe made from temper-
ature resistant material (to 95° C).
Install water discharge as follows
•
Install a drain hose 1 1/4 ", 250 -. 1000 mm long, into a
pressure-free outlet according to DIN EN 1717. Please
ensure that ascending vapor does not condensate on
the humidifier`s housing.
•
Fit water drain hose over the pump drain hose and fas-
ten to the housing drain connection.
2 grounding clips are fixed on the inn er surface of the housing
drain connection. Du ring blow-down, the grou nding clip is in
direct contact with the water and shunts potential residual elec-
tric currents away from the housing.
There is a 3mm-wide crack between the pump drain hose jacket
and the inner surface of th e housing drain connection . If water
collects in the base plate , it will flow through this crack into the
drainage system.
Pump drain hose
Case drain hose
grounding
Summary of Contents for MiniSteam MS 10
Page 1: ...Electrode Steam Humidifier MiniSteam MS ENU MS EN Manual...
Page 16: ...Page 16 5 1 1 Fitting measures Wall Distances mm 150...
Page 18: ...Page 18 5 3 Unit Dimensions Water inlet Waste water connection Cable entries...
Page 39: ...Page 39 10 EC Declaration of Conformity...
Page 45: ...Page 45 15 View of housing...
Page 46: ...12 2004...