Page 30
Maximum current draw of the FlexLine stan-
dard models and the required fusing resulting
from that can be taken from the table below.
7.2 Cable connections
The table below shows the number and
dimensioning of the cable connections pro-
vided by the various FlexLine housing types.
Characteristics of metric cable connec-
tions
*) Multiple seal insert
Model
Current draw [A]
Fusing
[A]
FLP05
9.0 - 9.9
3 x 16
FLP08
15.0 - 16.3
3 x 20
FLP15
15.6 - 17.1
3 x 20
FLP25
25.9 - 28.3
3 x 32 (35)
FLP30
31.2 - 34.1
3 x 35
FLP40
41.5 - 45.4
3 x 50
FLP50
51.8 - 56.6
3 x 63
Model
M25
PG
M25
with
MSI*)
M40
PG
Ø
25
filler
plug
FLP05
FLP08
1
1
0
3
FLP15/25
1
1
0
3
FLP30/40
FLP50
0
1
1
3
Thread
Wrench
size [mm]
Cable diameter
supported [mm]
M25x1.5
30
9 - 17
M25x1.5
with MSI*)
30
6 (3 x)
M32x1.5
36
13 - 21
M40x1.5
46
16 - 28