Page 24
•
Position the steam manifold to ensure uniform steam
distribution in the air duct.
•
Install the steam manifold horizontal with it ensure a
clean steam out.
•
By tilting the steam manifold 30 - 45° towards the air
flow direction, the minimum upper clearance can be
reduced to 70 mm.
Air Duct
Note on Installation
low
Different lengths in the air flow direc-
tion side by side
narrow, high
Identical lengths one on top of the
other. Staggered laterally if possible.
square
Identical lengths, staggered vertically
and laterally
low, very wide Facing each other.