5.4 Steam Manifold
Note:
Shown installation and position dimensions are based on
experimental values. Special environmental conditions could
require adjustments.
Please note:
•
Install the steam manifold as close as possible to the
steam humidifier in order to minimize steam loss
through condensation.
Note:
For steambath generators Type HyLine/CompactLine:
•
Install the steam manifold safe from contact with people
in order to prevent injuries or burns.
•
Do not install the steam manifold near a temperature
sensor or inaccurate readings may result.
The number and size of appropriate steam manifolds, as well
the nominal width of their respective steam and condensate
hoses, are found in the tables below.
HyLine:
CompactLine:
DemiLine:
Type
Steam
Manifold
Steam
hose
Condensat
Hose
HY05-HY17
1x25
DN25
DN12
HY23-HY30
1x40
DN40
DN12
HY45-HY60
2x40
2xDN40
2xDN12
HY90-HY116
4x40
4xDN40
4xDN12
Type
Steam
Manifold
Steam
Hose
Condensate
Hose
C6-C17
1x25
DN25
DN12
C22, C30
1x40
DN40
DN12
C45**
2x40
DN40
DN12
C58
2x40
2xDN40
2xDN12
Type
Steam
Manifold
Steam
Hose
Condensate
Hose
DL6-12*
1x25
DN25
DN12
DL18-27
1x40
DN40
DN12