Page 17
5.2 Fan Unit (option)
Note:
The fan unit should be positioned to avoid drafts. A mini-
mum height of 2 m is generally sufficient.
•
Install the fan unit directly on a wall.
•
The fan unit is installed above the steam humidifier.
•
When using multiple fan units, do not exceed a maxi-
mum distance of 5 m from the steam humidifier.
•
Observe the clearances specified in the diagrams
below.
Fan unit, wall installation
Side view, wall-mounted fan unit
Type
Fan Unit
DemiLine 6
VG 08
DemiLine 9-12
VG 17
DemiLine 18-27
VG 30
(all dimensions in mm)