SPA
Page 40
»
Finish entry of value with
»
Press
twice to exit the submenu
»
the modification must be confirmed to be permanently saved;
to do this press
»
press
to exit the menu
Values between 0 and 65 °C are programmable. The preset value for
G2 is 45 °C.
6.2.2.4
Hysteresis Exhaust Fan (G3)
This parameter sets the release point for the fan during steam bath
operation. The fan shuts off when the steam bath temperature falls to
the value “Steam Bath °C Set Value (G2) - Hysteresis Exhaust Fan
(G3)“.
Example: G2 is set to 45 °C and G3 is set to 2 K. The fan switches off
at 43 °C.
The preset value is 1 K. Values between 0 and 10 K are possible.
6.2.2.5
Time Essence Injection (G4)
This parameter is used to set the duration [sec.] of essence delivery.
Values between 0 and 25 seconds may be programmed. The preset
value is 2 seconds.
Note:
For Parameters G2 - G4, please also consult the graph in Sec-
tion “Steam Bath - Temperature Control”.
6.2.2.6
Interval Time Essence Injection (G5)
Use this parameter to set the interval period [min.] between essence
injections.
Values between 0 and 99 minutes are possible. The preset value is 5
minutes.
Steam Bath
°C Set Value
G2: 042 °C
ESC
Steam Bath
°C Set Value
G2: 42 °C
ESC
Confirm change
with Enter
yes