background image

6

Electrical Installation

MAIN BREAKER PANEL

LINE 1

N

LINE 2

OPTION 1

MAIN BREAKER PANEL

OPTION 2

20-60AMP HARDWIRED

Option 1 shows the power from GFCI breaker installed into main service panel to a service disconnect 
within line-of-site of the spa. If the manufacturer of your homes main breaker panel makes a GFCI 
breaker, you may be able to add it to an open slot in the panel.

Option 2 shows the power from main service panel to a GFCI subpanel within line-of-site of the spa. 

 

(Note: Most local codes will allow a GFCI subpanel to be a disconnect. If this is not the case in your 
installation, a disconnect must be provided.)

REFER TO GFCI WIRING DETAIL ON 

PAGE 8

GFCI Installed in Main Service Panel

Subpanel GFCI Installed

PORTABLE SPA

INLINE SPA DISCONNECT

20-60AMP HARDWIRED

GFCI DISCONNECT

LINE 1

N

LINE 2

INLINE SPA DISCONNECT

TO PORTABLE SPA

REFER TO GFCI WIRING DETAIL ON PAGE 8

Summary of Contents for BALBOA BP7 Series

Page 1: ...BP SERIES BALBOA TM Balboa BP7 SERIES Installation Operation Manual By...

Page 2: ...ng 18 Electrical Installation 5 7 Circuit Board Wiring Diagram 13 GFCI Wiring Detail 7 Pump Cord Configuration 9 Important Safety Instructions 3 4 Spaside Installation 10 spaTouch Icon Programming 19...

Page 3: ...the terminal box Refer to NEC and local codes A bonding lug is provided on the control box to permit connection of a solid copper bonding conductor between this point and any equipment metal enclosur...

Page 4: ...quires proper ventilation and is intended for outdoor use only For Permanently Installed Units For Permanently Installed Units not Provided with an Internal Disconnecting Method For Units with Gas Hea...

Page 5: ...cian must accomplish the electrical installation in accordance with the National Electric Code NEC Article 680 and any local codes in effect at the time of installation The NEC and most local codes re...

Page 6: ...o add it to an open slot in the panel Option 2 shows the power from main service panel to a GFCI subpanel within line of site of the spa Note Most local codes will allow a GFCI subpanel to be a discon...

Page 7: ...OUND BUS BAR LINE LUG 1 LINE LUG 2 INCOMING SERVICE CONDUCTORS FROM MAIN PANEL NEUTRAL GROUND TO SPA CONTROL SYSTEM LOAD LOAD NEUTRAL MUST BE CONNECTED DIRECTLY TO GFCI AS SHOWN GFCI Wiring Detail The...

Page 8: ...at the time of installation Power Connection Ground Lug OPTIONAL N L2 L1 GR N A BLK L1 RED L2 WHT N 120 VOLT ELECTRICAL SERVICE REQUIREMENTS Assure DIP switches A2 A3 are OFF or in the down position...

Page 9: ...on is for single speed pump circuits circulation pumps ozones blowers and accessories Black Hot Line White Common Green Ground Black Hot Line White Common Green Ground Pump Cord Connections Pump Singl...

Page 10: ...s straight and adhere to the spa shell Fig 2 The mounting area must be above the maximum water level of the spa and in an area with good drainage to prevent any standing water on or around the spaside...

Page 11: ...ith the internet using a wifi module If no main connections are available you may use the Y cable provided with the wifi module kit 34 0216E Note If you experience poor operation via the wifi module i...

Page 12: ...wiring diagram that was included with your unit for the correct component location to properly convert to 120V Figure 1 J79 J45 J54 J77 J78 120V Component Volts Amps From To P1 1 or 2 spd 120V 12A Are...

Page 13: ...13 Wiring Diagram HEATER White to Location 2 for 240V White to Location 4 for 120V Both Pumps must be same voltage...

Page 14: ...None None None F 10 Yes J21 None None None F 11 Yes J21 None None None F 12 Yes J21 None None None None F 13 Yes J21 None None None None F 14 Yes J21 None None None None F 15 Yes J21 None None None N...

Page 15: ...21 None None F 31 Yes J21 None None F 32 None None None F J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 2 Spd J9 1 Spd J9 1 Spd J14 1 Spd J14 1...

Page 16: ...the current Setup SET SET SET SET SET SET SET While the Set Temperature is still ashing press Light TEST will now appear in the LCD rst SET RANGE Main Screen Main Screen READY RANGE FLTR 1 SET Approx...

Page 17: ...s a single Temperature Button Test Menu Access S1 Switch 1 ON Service Technician ONLY With system on or OFF move DIP Switch 1 on S1 on the Main circuit board to ON The system will enter Test Mode Movi...

Page 18: ...the Setup screen will allow changing the Setup from 1 to any number established by the Manufacturer Changing the Setup may require wiring changes as well TP800 TP900 spaTouch Menued Panel Programming...

Page 19: ...screen press the Up or Down icon to select the desired Setup Number then press the Check Mark icon to con rm and to have the spa restart After the system restarts you may see a message that The setti...

Page 20: ...e Pump 2 or Aux button if you have a 2nd pump to turn it on The pumps will now be running in high speed to facilitate priming If the pumps have not primed after 2 minutes and water is not owing from t...

Page 21: ...Freeze related damage is not covered by the warranty Winterizing Chemical Water Treatment Your dealer is familiar with local water conditions and which chemicals are compatible with and designed spec...

Page 22: ...either button while the set temperature is displayed will increase or decrease the set temperature by 1 F The temperature is adjustable between 80 F 104 F 26 C 40 C or 50 F 99 F 10 C 37 C See Dual Te...

Page 23: ...water temperature heat as needed and refresh the temperature display This is known as polling Ready will be displayed REST MODE Will only allow heating during programmed filter cycles The temperature...

Page 24: ...off to the spa unplug the two sensors from the circuit board and exchange their positions i e plug the one that was in the Sen A jack into the Sen B jack and vice versa 5 Power up the spa if the erro...

Page 25: ...to On Power switch in Off position Set to On Components not plugged in Plug in components Power cord not plugged in Plug in power cord Over or High Temperature Protection On Refer to Spa Side Messages...

Page 26: ...rature Protection On Refer to Spa Side Messages Current Limiting On 120V Systems will not heat if High Speed or Blower is on Contact your local dealer No Power Reset breaker at service panel Low Water...

Page 27: ...r freight collect When sent to Hydro Quip the product must be accompanied by the sales receipt or other proof of the purchase date as well as the sender s name mailing address daytime phone number and...

Page 28: ...28 85 0080C Rev 02 02 21...

Reviews: