Quick Reference Guide
Appendix B: Troubleshooting Guide
Alert Troubleshooting
Water Window Alert
During times of high ET, the water window you selected may not
have enough time in it to adequately irrigate all zones.
To correct this:
1.
Increase the water window.
2.
Increase the number of days to irrigate.
3.
Change the station program parameters or adjust to reduce the
required amount of water for each zone.
Day Interval Alert
1.
During times of high ET, the number of days you allow irrigation
may not be enough to adequately irrigate all zones.
2.
To correct this:
–
Increase the number of days to irrigate.
–
Change the station program parameters or adjust to reduce
the required amount of water for each zone.
Communication alert:
Call HydroPoint Data Systems Customer Service at: 800-362-8774.
Electrical Alert
Most likely, this is caused by a blown solenoid or wiring problem.
To correct this:
1.
Check the solenoid on each affected valve.
2.
Check the wiring from the controller to each valve.
3.
If the above solutions do not fix the problem, call your local
irrigation repair company or HPDS distributor for more
information.
Appendix B
B
89