Hydromatic S Installation And Service Manual Download Page 7

7

bottom  of  stator  housing  and
remove plug in top of hous ing
to allow air to enter.

3. After  chamber  is  drained,

remove 

hold-down 

bolts 

and  lift  off.  Use  care  in 
lifting  as  the  seal  failure 
con nect ing  wire  must  be 
dis con nect ed  before  housing
is  com plete ly  removed.  See
sec tion al drawing.

4. Set  assembly  on  bench  and 

re move con nec tion box. When
box  is  lifted  off,  connection
wires  to  motor  will  be
exposed.  These  wires  will
probably  be  burned,  but  each
wire  is  tagged  with  a  metal
marker  giving  wire  num ber.
Cut the wires.
If  the  leads  to  the  connection
box  are  burned,  a  complete
new  con nec tion  box  with  new
wire  must  be  used.  The  wires
are  potted  in  with  sealing 
com pound and a new unit must
be obtained from the factory.

5. The  stator  is  held  in  the 

housing  with  a  bolted-in
clamp ring. 

6. After  ring  is  removed  turn

hous ing  upright  and  bump  on
hard wood blocks. This should
jar the stator loose and allow it
to drop out.

7. Thoroughly  clean  hous ing

before  replacing  new  stator.
Replace  sta tor  and  make  all
wire con nec tions to connection
box  before  re plac ing  housing
on pump. This is im por tant as
leads  must  be  tucked  behind
the  windings  by  using  hands
up through rotor core.

IMPORTANT: 

Use 

only 

compression  type  insulated
connectors on the wires. Do not
tape leads as oil will de te ri o rate
the  tape  and  cause  dam age  to
stator and bear ings.

8. Drain  oil  from  cham ber.  If 

oil  is  clean  and  no  wa ter 
is  present,  seals  can  be 
considered sat is fac to ry to re use.

9. Check top bearing. If clean and

does  not  turn  rough,  bearings
can  be  reused  and  it  is  not 
necessary 

to 

com plete ly 

dismantle  pump  to  change
bearings.  If  bearings  are 
dam aged with dirt or heat they
must 

be 

replaced. 

See 

ad di tion al  instructions  on 
re plac ing  seals  and  bearings.
Re mem ber  to  reinstall  the
upper bearing load spring.

10.Replace  stator  hous ing  onto

seal chamber and bolt in place.
Be  sure  seal  failure  wire 
is con nect ed before housing is
as sem bled.
Be  sure  O-ring  seal  has  been
replaced. If O-ring is nicked or
cut  replace  the  new  rights. 
This ap plies to all O-rings used
in as sem bly.

11.After all leads are reconnected

in  the  con nec tion  box  make  a
high  voltage  ground  test  on
each  wire.  The  only  wire  that
should  show  ground  is  the
green  power  lead  and  the
ground  lead  in  the  aux il ia ry
control cable.

12.For  safety,  complete  pump

should  be  air  checked  under
water  for  leaks.  If  seals  were
OK,  refill  seal  chamber  with
oil.  Lay pump on side for this
oil  filling,  with  oil  fill  hole
upright. Do not completely fill;
leave  oil  about  1  inch  below
plug hole. Use only high grade
transformer  oil  or  regular
Hydromatic submersible oil in
this  chamber.  Replace  plug;
use  Permatex  on  threads.
Install  air  valve  in  top  plug
opening of motor housing and
charge  housing  with  about  10
psi of air. Be sure air is dry. Do
not  use  air  line  where  water
may  be  trapped  in  the  line.
Submerge complete unit under
water and check for leaks.

Summary of Contents for S

Page 1: ...25 304 1 2010 Pentair Pump Group Inc Installation and Service Manual NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system For use with product built with Regal Beloit Marathon motor ...

Page 2: ...erate without damage but the seal should be checked immediately after failure is indicated NOTE Failure to install such a device negates all warranties by Hydromatic Pump The S submersible pump is supplied for 1 and 3 phase and for 200 230 460 or 575 volts Pump is supplied with 30 feet of power cord and or 30 feet of auxiliary control cord Longer cable lengths can be furnished but must be specifie...

Page 3: ...controls one set at turn off one set at turn on for one pump one set at turn on for two pumps and one set at turn on for three pumps Pumps alternate each successive cycle Three pumps operate together only if sump level rises to the fourth control second override This control also brings on the third pump in case of failure of either or both of the first two pumps Alarm Controls The alarm level is ...

Page 4: ... between sump and panel a Walkie Talkie radio is useful Installing 3900 Mercury Switch Controls The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box Cord snubbers are used to hold the cord in place Control lever can be changed at any time by loosening the snubber and readjusting cord length In either simplex or duplex system the lowe...

Page 5: ...ed for use in making the installation All wires should be checked for grounds with an ohmmeter or Megger after the connections are made This is important as one grounded wire can cause considerable trouble Figure 1 CONNECTION DIAGRAM FOR LEADS IN MOTOR AND CONNECTION BOX Y WYE MOTOR CONNECTIONS 230 VOLTS 460 VOLTS GREEN GREEN L3 L2 L1 L3 L2 L1 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 HEAT SENSORS AND S...

Page 6: ...f operation 6 Turn both H O A switches to Auto position and allow sump to fill to the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until level drops to turn off point 8 Repeat this operation cycle several times before leaving the job 9 Check voltage when pumps are operating and check the amp draw of each pump Check amps on each wire ...

Page 7: ...8 Drain oil from chamber If oil is clean and no water is present seals can be considered satisfactory to reuse 9 Check top bearing If clean and does not turn rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on replacing seals and bearings Remember to reins...

Page 8: ...e This will force out lower seal if not already removed 9 Remove snap ring that holds upper seal Pull seal if it is free If not free it can be forced off when shaft is removed 10 Remove 4 bolts that hold bearing housing in place Set assembly in upright position and bump end of shaft on hardwood block This will push the bearing from the housing and will force upper seal from shaft 11 Use bearing pu...

Page 9: ...p in the closed position Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver proper capacity 1 Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can operate in reverse direction without much noise o...

Page 10: ...P 200 3 60 1 1150 RPM For pumps manufactured after 11 12 73 24407C225 Stator 1 2 HP 1 HP 230 460 3 60 1 1150 RPM 24407C226 Stator 1 2 HP 1 HP 575 3 60 1 1150 RPM 14694 203 1 Stator 3 4 HP 1 HP 200 1 60 1 1750 RPM 14694 003 1 Stator 3 4 HP 1 HP 230 1 60 1 1750 RPM 24407C212 Stator 3 4 HP 1 HP 200 3 60 1 1750 RPM 24407C213 Stator 3 4 HP 1 HP 230 460 3 60 1 1750 RPM 14695 603 1 Stator 3 4 HP 1 HP 575...

Page 11: ...11 2 3 4 6 7 8 9 11 12 14 15 16 17 18 19 20 21 22 23 24 25 48 26 27 28 29 33 32 31 30 46 45 44 41 43 42 40 38 37 36 34 35 47 30 49 10 1 S ...

Page 12: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Page 13: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Page 14: ...rdance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other tha...

Page 15: ......

Page 16: ...g Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well Yes No Are Floats Set to Engineer s Specs Yes No Are Floats Wired for Proper Seq...

Reviews: