Hydromatic S Installation And Service Manual Download Page 2

2

Thank  you  for  purchasing  your
Hydromatic

®

pump.  To  help

ensure  years  of  trouble-free
operation, 

please 

read 

the

following manual carefully.

Before Operation:
Read  the  following  in struc tions
care ful ly.  Reasonable  care  and
safe meth ods should be practiced.
Check 

local 

codes 

and

requirements before installation.

Attention:
This  manual  contains  important
information  for  the  safe  use  of
this  product.    Read  this  manual
completely  before  using  this
product  and  refer  to  it  often  for
con tin ued  safe  product  use.
DO  NOT  THROW  AWAY  OR
LOSE THIS  MAN U AL.    Keep  it
in  a  safe  place  so  that  you  may
refer to it often.

Unpacking Pump:
Remove pump from carton. When
un pack ing 

unit, 

check 

for

con cealed  damage.  Claims  for
damage  must  be  made  at  the
receiving end through the delivery
carrier.  Dam age  cannot  be
processed from the factory.

WARNING:  Before  handling
these  pumps  and  controls,
always  disconnect  the  power
first.  Do  not  smoke  or  use
sparkable  electrical  devices  or
flames  in  a  septic  (gaseous)  or
possible septic sump.

Pumps in Storage or Not
Operating:
Pumps with carbon ceramic seals
must  have  impellers  manually
rotated  (6  revolutions)  after 
setting  nonoperational  for  3
months  or  longer  and  prior  to
electrical start-up.
Pumps with tungsten carbide seals
must  have  impellers  manually
rotated  (6  revolutions)  after 
setting  non-operational  for  3
weeks  or  longer  and  prior  to 
electrical start-up.

Seal Failure:
An  electrode  is  installed  in  the
seal  chamber  so  if  any  water
enters  the  chamber  through  the
first  seal  the  electrode  will  be
energized  and  a  signal  will  be
transmitted  to  the  sens ing  unit  at
ground  surface,  causing  an  alarm
function to energize.
In  operation  the  seal  failure  unit
indicates  only  that  there  is  some
water  in  the  seal  chamber.  The
pump  will  continue  to  operate
without  damage,  but  the  seal
should  be  checked  im me di ate ly
after failure is indicated.

NOTE:  Failure  to  install  such 
a  device  negates  all  warranties 
by Hydromatic.

Pump:
The  S  submersible  pump  is 
sup plied for 1 and 3 phase and for
200, 230, 460 or 575 volts. Pump
is sup plied with 30 feet of power
cord  and/or  30  feet  of  auxiliary
control cord. Longer cable lengths
can  be  furnished  but  must  be 
specified  at  time  of  order.  Power
cable is 4 wire with the green wire
for ground. Be sure green wire is
connected to a good ground such
as  water  pipe  or  ground  stake. 
The auxiliary cable for seal failure

General
Information

and  heat  sensors  is  also  4  wire
color coded.

Heat Sensors:
All motors have heat sensor units
embedded in the motor winding to
detect  excessive  heat.  The  heat
sen sors are set to trip at 105°C, so
will not operate if dangerous heat
occurs. The sensors automatically
reset  when  motor  cools  to 
safe temperature.
The  sensors  are  connected  in
series  with  the  motor  starter  coil
so that the starter is tripped if heat
sensor opens. The motor starter is
equipped with overload heaters so
all normal over loads are protected
by the starter.

NOTE: Failure to install such a
device negates all warranties by
Hydromatic.

IMPORTANT: 

If 

Hydromatic

electrical  starting  equipment  is
not  supplied  the  heat  sensor 
circuit  must  be  connected  in
series  with  the  starter  coil  or
warranty  on  motor  is  void. 
Connection diagram is included
in this manual.

Sump Level Control:
Sump  level  is  controlled  by
Hydromatic 3900 mercury switch
controls.  The  3900  control  is  a
mer cu ry  tube  switch  sealed  in  a
solid polyurethane float. The float
is held in position in the sump by
weight at tached to the power cord
above the float. The cord supports
the float and is adjusted for height
from the sur face.
Typical  duplex  systems  use  three
controls:  one  set  at  turn-off,  one
set  at  turn-on  for  one  pump,  and
one set for turn-on for two pumps.
Pumps al ter nate operation on each
successive cycle.

Summary of Contents for S

Page 1: ...25 304 1 2010 Pentair Pump Group Inc Installation and Service Manual NOTE To the installer Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system For use with product built with Regal Beloit Marathon motor ...

Page 2: ...erate without damage but the seal should be checked immediately after failure is indicated NOTE Failure to install such a device negates all warranties by Hydromatic Pump The S submersible pump is supplied for 1 and 3 phase and for 200 230 460 or 575 volts Pump is supplied with 30 feet of power cord and or 30 feet of auxiliary control cord Longer cable lengths can be furnished but must be specifie...

Page 3: ...controls one set at turn off one set at turn on for one pump one set at turn on for two pumps and one set at turn on for three pumps Pumps alternate each successive cycle Three pumps operate together only if sump level rises to the fourth control second override This control also brings on the third pump in case of failure of either or both of the first two pumps Alarm Controls The alarm level is ...

Page 4: ... between sump and panel a Walkie Talkie radio is useful Installing 3900 Mercury Switch Controls The controls are supported by a mounting bracket that is attached to sump wall or cover or to the NEMA 4 junction box Cord snubbers are used to hold the cord in place Control lever can be changed at any time by loosening the snubber and readjusting cord length In either simplex or duplex system the lowe...

Page 5: ...ed for use in making the installation All wires should be checked for grounds with an ohmmeter or Megger after the connections are made This is important as one grounded wire can cause considerable trouble Figure 1 CONNECTION DIAGRAM FOR LEADS IN MOTOR AND CONNECTION BOX Y WYE MOTOR CONNECTIONS 230 VOLTS 460 VOLTS GREEN GREEN L3 L2 L1 L3 L2 L1 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 5 4 HEAT SENSORS AND S...

Page 6: ...f operation 6 Turn both H O A switches to Auto position and allow sump to fill to the override control level 7 Turn both switches to Auto position and both pumps should start and operate together until level drops to turn off point 8 Repeat this operation cycle several times before leaving the job 9 Check voltage when pumps are operating and check the amp draw of each pump Check amps on each wire ...

Page 7: ...8 Drain oil from chamber If oil is clean and no water is present seals can be considered satisfactory to reuse 9 Check top bearing If clean and does not turn rough bearings can be reused and it is not necessary to completely dismantle pump to change bearings If bearings are damaged with dirt or heat they must be replaced See additional instructions on replacing seals and bearings Remember to reins...

Page 8: ...e This will force out lower seal if not already removed 9 Remove snap ring that holds upper seal Pull seal if it is free If not free it can be forced off when shaft is removed 10 Remove 4 bolts that hold bearing housing in place Set assembly in upright position and bump end of shaft on hardwood block This will push the bearing from the housing and will force upper seal from shaft 11 Use bearing pu...

Page 9: ...p in the closed position Check in sump to be sure control is free 3 Selector switch may be in the Hand position Pump does not deliver proper capacity 1 Discharge gate valve may be partially closed or partially clogged 2 Check valve may be partially clogged Raise level up and down to clear 3 Pump may be running in wrong direction Low speed pumps can operate in reverse direction without much noise o...

Page 10: ...P 200 3 60 1 1150 RPM For pumps manufactured after 11 12 73 24407C225 Stator 1 2 HP 1 HP 230 460 3 60 1 1150 RPM 24407C226 Stator 1 2 HP 1 HP 575 3 60 1 1150 RPM 14694 203 1 Stator 3 4 HP 1 HP 200 1 60 1 1750 RPM 14694 003 1 Stator 3 4 HP 1 HP 230 1 60 1 1750 RPM 24407C212 Stator 3 4 HP 1 HP 200 3 60 1 1750 RPM 24407C213 Stator 3 4 HP 1 HP 230 460 3 60 1 1750 RPM 14695 603 1 Stator 3 4 HP 1 HP 575...

Page 11: ...11 2 3 4 6 7 8 9 11 12 14 15 16 17 18 19 20 21 22 23 24 25 48 26 27 28 29 33 32 31 30 46 45 44 41 43 42 40 38 37 36 34 35 47 30 49 10 1 S ...

Page 12: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Page 13: ...__________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ ______________________________________________ _____________...

Page 14: ...rdance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such service d to units which are not installed in accordance with applicable local codes ordinances and good trade practices e if the unit is moved from its original installation location f if unit is used for purposes other tha...

Page 15: ......

Page 16: ...g Line Voltage _________________________________Actual ___________________________________ Voltage to Pumps _____________________________________Actual ___________________________________ Type of Junction Box __________________________________Manufacturer of Junction Box ______________ Are Floats Installed in Wet Well Yes No Are Floats Set to Engineer s Specs Yes No Are Floats Wired for Proper Seq...

Reviews: