Regulation (EU) n° 517/2014 of 16/04/14 on fluorinated greenhouse gases and
repealing Regulation (EC) n° 842/2006
Leak checks
1.
Operators of equipment that contains fluorinated greenhouses gases in quantities of 5 tons of CO
2
, equivalent
or
more and not contained in foams shall ensure that the equipment is checked for leaks.
2. F
or equipment that contains fluorinated greenhouse gases in quantities of 5 tons of
CO
2
equivalent or more, but
of less than 50 tons of
CO
2
equivalent: at least every 12 months.
Picture of the equivalence CO
2
1.
Load in kg and Tons amounting CO
2
.
Load and Tons amounting CO
2
Frequency of test
From 2 to 30 kg load = from 5 to 50 Tons
Each year
Concerning the Gaz R32,7.41kg amounting at 5 tons of CO
2
, commitment to check each year.
Training and certification
1.
The operator of the relevant application shall ensure that the relevant personnel have obtained the necessary
certification, which implies appropriate knowledge of the applicable regulations and standards as well as the
necessary competence in emission prevention and recovery of fluorinated greenhouse gases and handling safety
the relevant type and size of equipment.
Record keeping
1.
Operators of equipment which is required to be checked for leaks, shall establish and maintain records for each
piece of such equipment specifying the following information:
a) T
he quantity and type of fluorinated greenhouse gases installed
;
b)
The quantities of fluorinated greenhouse gases added during installation, maintenance or servicing or due to
leakage;
c) W
hether the quantities of installed fluorinated greenhouse gases have been recycled or reclaimed, including the
name and address of the recycling or reclamation facility and, where applicable, the certificate number;
d)
The quantity of fluorinated greenhouse gases recovered
e) T
he identity of the undertaking which installed, serviced, maintained and where applicable repaired or
decommissioned the equipment, including, where applicable, the number of its certificate;
f) T
he dates and results of the checks carried out;
g) I
f the equipment was decommissioned, the measures taken to recover and dispose of the fluorinated
greenhouse gases.
2. The operator shall keep the records for at least five years, undertakings carrying out the activities for operators
shall keep copies of the records for at least five years.
Summary of Contents for 7029988
Page 8: ...6 2 Wymiary mm Model Hydro S 5 Model Hydro S 8 Hydro S 10 ...
Page 9: ...7 Model Hydro S 12 ...
Page 24: ...22 8 Schemat budowy pompy 8 1 Widok urządzenia rozebranego Model Hydro S 5 ...
Page 32: ...30 2 Dimension mm Model Hydro S 5 Model Hydro S 8 Hydro S 10 ...
Page 35: ...33 3 5 Typical arrangement Note This arrangement is only an illustrative example ...
Page 47: ...45 8 Exploded Diagram 8 1 Exploded Diagram Model Hydro S 5 ...
Page 55: ...53 2 Ausmaße mm Model Hydro S 5 Model Hydro S 8 Hydro S 10 ...
Page 69: ...67 8 Explosionszeichnung und Wartung 8 1 Explosionszeichnung Hydro S 5 ...
Page 75: ......
Page 76: ...A0111HYSR302 ...