EN
25
DE/EN/FR 18.055.H.7/07.19
5.3.2
Setting a hysteresis
(Only possible if the switch-back mode is set to "hysteresis".)
pressure
display
press OFF
key
display
set hysteresis
= larger value
= smaller value
5.3.3
Setting a switch-back point
(Only possible if the switch-back mode is set to "switch-back point".)
pressure
display
press OFF
key
display
set switch-back point
= larger value
= smaller value
Notes:
If "
LOC
" appears in the display when trying to alter the settings, programming
is disabled.
Corrective action:
set hardware and software programming enable to "
ON
".
(See point 8 "Programming enable")
If the "+" or "-" key is held down during alteration, the value automatically
advances in larger increments.
If a setting has been altered, "
PROG
" appears briefly in the display when the
display switches over. The new setting is then saved in the unit.