ContaminationSensor – CS 2000 series
HYDAC Filtertechnik GmbH
en
Page 40
BeWa CS2000 3117721e en.doc
2008-03-28
IP address part 3:
current setting: 14
new setting (press Return only to keep setting): 16
current setting: 16
IP address part 4:
current setting: 150
new setting (press Return only to keep setting): 36
current setting: 36
In this example, the IP address was changed from 129.42.14.150 to 192.168.16.36.
8.3.4.6 Dry-running
protection
p = Pump protection
enables a pump controlled by the ContaminationSensor via
relay 1 to be protected against running dry in operating modes M1, M3 and M4. If
there is not a sufficient volumetric flow after the start of the measurement or after a
flow error occurs, the pump is switched off by relay 1 after expiration of the
measurement interval during which the pump protection time runs down. This
means the pump is only switched off after two measurement intervals have expired.
Entering 0 deactivates this function!
actual Pump protection time : 0 s
New value for Pump protection time (press Return only to keep setting):
10
Actual value for Pump protection time: 10
(In the example, the deactivated function was activated and 10 s entered as the
time.)
8.3.4.7 PLC
interface
o = PLC Output Format
selects whether the NAS/SAE class (1 value) or the ISO
code (3 values) is output via the PLC interface.
Additionally, the output frequency can be varied. (See chapter 9.)
Current PLC Output Format: ISO
Enter 1 for SAE or 2 for ISO (press Return only to keep setting):
1
Selected PLC Output Format: SAE
Current PLC Output Format: SAE
PLC Output Frequency Divider: 1
New value (1..4) for PLC output frequency divider (press Return only to keep
setting): 2
PLC output frequency divider set to: 2