Installation and Operation
HYDAC Filtertechnik GmbH
en
Page 36
BeWa CS1000 3247149k en.doc
2006-04-06
8.8
Switching Behavior of the Switching Output
Mode 1 (M1)
Switching output CLOSED
Switching output OPEN
-
Always open
Mode 2 (M2)
Switching output CLOSED
Switching output OPEN
BEYOND
Beyond limit
≥
upper limit
After switching the unit on or starting a
measurement
Opens again when
≤
lower limit
BELOW
Below limit
≤
lower limit
After switching the unit on or starting a
measurement
Opens again when
≥
upper limit
WITHIN
Within band
Lower limit
≤
measured value
≤
upper
limit
After switching the unit on or starting a
measurement
Opens again when < lower limit
or
> upper limit
OUTSDE
Outside band
Measured value
≤
lower limit or
Measured value
≥
upper limit
After switching the unit on or starting a
measurement or
Lower limit < measured value
< upper limit
OFF
No switching
-
Always open
Mode 2 (M2)
For 3-digit ISO Code
Switching output CLOSED
Switching output OPEN
BEYOND
Beyond limit
A value
≥
respective upper limit
After switching the unit on or starting a
measurement
Opens again when all values
≤
respective lower limit
BELOW
Below limit
All values
≤
respective lower limit
After switching the unit on or starting a
measurement
Opens again when a value
≥
respective
upper limit
WITHIN
Within band
Respective lower limit
≤
all values
≤
respective upper limit
After switching the unit on or starting a
measurement
Opens again when the respective lower
limit < all values < upper limit
OUTSDE
Outside band
A value
≤
respective lower limit
or
a value
≥
respective upper limit
After switching the unit on or starting a
measurement
Opens again when the respective lower
limit < all values < upper limit
OFF
No switching
-
Always open