TransformerCare Unit
Hydraulic functions
7
Item
Designation
Example
mbar
(absolute)
1
Normal operating pressure level fluctuates
between a lower (minimum oil level in the
degasification and dewatering unit) and an
upper pressure (maximum oil level).
110 … 230
2
The alarm pressure (SP2) should be ~ 20 %
above the pressure currently shown (upper
pressure).
At least 20 mbar higher than the actual
pressure.
270
3
Stopping pressure (SP1): 600 mbar. After
expiry of a preset delay (K1), the TCU
deactivates automatically.
600
4
Atmospheric pressure
1013
5
The signal lamp illuminates
6
Absolute pressure
7
Absolute vacuum
0
HYDAC FILTER SYSTEMS GMBH
en
Page 19 / 64
BeWa TCU 3472805b en 2011-07-05.doc
2011-07-05