Series EC-5 — 5.6  K-factor

Extended Coverage Horizontal Sidewall Sprinklers

Quick & Standard Response (Light Hazard)

Page 1 of 6 

AUGUST 2018 

TFP298

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The Series EC-5, Extended Cover-

age Horizontal Sidewall Sprinklers 

are extended coverage, decorative 

3 mm glass bulb type spray sprin-

klers designed for use in hydraulically 

calculated sprinkler systems in light 

hazard, commercial occupancies such 

as churches, restaurant seating areas, 

hotels, educational facilities, offices, 

etc. With their coverage up to 16 ft 

(4,9 m) wide by 24 ft (7,3 m) long and 

maximum deflector to ceiling distance 

of 18 in. (450 mm), they are designed 

for installation along a wall or the side 

of a beam and just beneath a smooth 

and level ceiling. Horizontal sidewall 

sprinklers are commonly used instead 

of pendent or upright sprinklers due 

to aesthetics or building construction 

considerations, where piping across 

the ceiling is not desirable.
The fast response thermal sensitiv-

ity rating of the Series EC-5, 3 mm 

Bulb Type Sprinklers provides a quick 

response extended coverage (QREC) 

rating for many of the coverage areas 

detailed in Tables B and C.
The recessed version of the Series 

EC-5 Extended Coverage Horizontal 

Sidewall Sprinkler utilizes a two-piece 

Style 50 Recessed Escutcheon. The 

Style 50 provides up to 3/8 in. (9,5 mm) 

of total adjustment from the flush side-

wall position. The adjustment provided 

by the Recessed Escutcheon reduces 

the accuracy to which the fixed pipe 

lengths to the sprinklers must be cut.

NOTICE

The Series EC-5 Sprinklers described 

herein must be installed and main-

tained in compliance with this docu-

ment, as well as with the applicable 

standards of the National Fire Protec-

tion Association, in addition to the stan-

dards of any other authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition. 

The installing contractor or sprinkler 

manufacturer should be contacted with 

any questions.

Sprinkler 

Identification 

Number

TY3302 - EC HSW, 5.6K

TY3302 is a redesignation for C3302.

Technical 

Data

Approvals

UL and C-UL Listed

FM and NYC Approved

(Refer to Table A for complete approval 

information. The approvals apply to the 

service conditions indicated in the Design 

Criteria section.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 in. NPT

Discharge Coefficient

K = 5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Ratings

Refer to Table A

Finishes

Sprinkler: Refer to Table D

Recessed Escutcheon: White Coated, 

Chrome Plated, or Brass Plated

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . Glass (3 mm dia.)

Compression Screw . . . . . . . . . . . . . . . . .Bronze

Deflector . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and water to flow.

Design 

Criteria

The Series EC-5 Extended Coverage 

Horizontal Sidewall Sprinklers must be 

installed and utilized in Light Hazard 

Occupancies, under smooth level 

ceilings as outlined in the applicable 

installation standard recognized by 

the Approval Agency (e.g., UL recog-

nizes NFPA 13, and FM recognizes the 

FM Loss Prevention Data Sheets). Only 

the Style 50 Recessed Escutcheon, as 

applicable, is to be used for recessed 

installations.

Summary of Contents for tyco EC-5 Series

Page 1: ...ide wall position The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut NOTICE The Series EC 5 Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the stan dards of any other ...

Page 2: ...ar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figures 1 the W Type 6 Sprinkler Wrench is to be ...

Page 3: ...Sprinklers that have been exposed to corrosive products of combustion but have not operated should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like mu...

Page 4: ...f Figures 1 and 2 4 Minimum spacing is for lateral distance between sprinklers located along a single wall Otherwise adjacent sprinklers i e sidewall sprinklers on an adjacent wall on an opposite wall or pendent sprinklers must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized 5 6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER TY...

Page 5: ...oating P N specify from Table D Recessed Escutcheon Specify Style 50 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE RAL9010 1 POLYESTER 4 SIGNAL WHITE RAL9003 POLYESTER 9 CHROME PLATE...

Page 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...