5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302) 

AND RECESSED HORIZONTAL SIDEWALL SPRINKLER (TY3302)

Response 

Rating

Coverage 

Area

1

 

Ft x Ft (m x m)

Minimum 

Flow

2

 

GPM (LPM)

Minimum 

Pressure

2

 

PSI (BAR)

Deflector-to- 

Ceiling 

Distance

3

 

In. (mm)

Sprinkler 

Temperature 

Rating 

°

F

Minimum 

Spacing

4

 

Ft (m)

Quick

16 x 16 (4,6 x 4,9)

26 (98)

21.6 (1,48)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Quick

16 x 16 (4,6 x 4,9)

26 (98)

21.6 (1,48)

4 to 12 (100 to 300)

200

8 (2,4)

Quick

16 x 18 (4,9 x 5,5)

29 (110)

26.8 (1,85)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Quick

16 x 20 (4,9 x 6,1)

32 (121)

32.7 (2,25)

4 to 18 (100 to 450)

135, 155

8 (2,4)

Standard

16 x 18 (4,9 x 5,5)

29 (110)

26.8 (1,85)

4 to 12 (100 to 300)

200

8 (2,4)

Standard

16 x 20 (4,9 x 6,1)

32 (121)

32.7 (2,25)

4 to 12 (100 to 300)

200

8 (2,4)

5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302)

NON-RECESSED

Quick

16 x 22 (4,6 x 6,7)

36 (136)

41.3 (2,85)

4 to 18 (100 to 450)

135

8 (2,4)

Standard

16 x 24 (4.9 x 7,3)

39 (148)

48.5 (3,34)

4 to 18 (100 to 450)

135

8 (2,4)

NOTE:

1.  Backwall (where sprinkler is located) by sidewall (length of throw).
2.  Requirement is based on minimum flow in GPM from each sprinkler. The indicted residual pressures are based on the nominal K-factor.
3.  The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4.  Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, 

on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

5.6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3302)

Response 

Rating

Coverage 

Area

1

 

Ft x Ft (m x m)

Minimum 

Flow

2

 

GPM (LPM)

Minimum 

Pressure

2

 

PSI (BAR)

Deflector-to- 

Ceiling 

Distance

3

 

In. (mm)

Sprinkler 

Temperature 

Rating 

°

F

Minimum 

Spacing

4

 

Ft (m)

Quick

16 x 16 (4,6 x 4,9)

26 (98)

22 (1,51)

4 to 12 (100 to 300)

155

8 (2,4)

Quick

16 x 18 (4,9 x 5,5)

30 (114)

29 (2,00)

4 to 12 (100 to 300)

155

8 (2,4)

Quick

16 x 20 (4.9 x 6,1)

33 (125)

35 (2,41)

4 to 12 (100 to 300)

155

8 (2,4)

NOTE:

1.  Backwall (where sprinkler is located) by sidewall (length of throw).
2.  Requirement is based on maintaining both minimum flow and minimum residual pressure.
3.  The centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figures 1 and 2).
4.  Minimum spacing is for lateral distance between sprinklers located along a single wall. Otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, 

on an opposite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

TABLE B 

UL AND C-UL LISTING 

DESIGN CRITERIA

TABLE C 

FM APPROVED 

DESIGN CRITERIA

Summary of Contents for tyco EC-5 Series

Page 1: ...ide wall position The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe lengths to the sprinklers must be cut NOTICE The Series EC 5 Sprinklers described herein must be installed and main tained in compliance with this docu ment as well as with the applicable standards of the National Fire Protec tion Association in addition to the stan dards of any other ...

Page 2: ...ar to the back wall and parallel to the ceiling The word TOP on the deflector is to face towards the ceiling Step 2 With pipe thread sealant applied to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 3 With reference to Figures 1 the W Type 6 Sprinkler Wrench is to be ...

Page 3: ...Sprinklers that have been exposed to corrosive products of combustion but have not operated should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before during and after installation Sprin klers damaged by dropping striking wrench twist slippage or the like mu...

Page 4: ...f Figures 1 and 2 4 Minimum spacing is for lateral distance between sprinklers located along a single wall Otherwise adjacent sprinklers i e sidewall sprinklers on an adjacent wall on an opposite wall or pendent sprinklers must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized 5 6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER TY...

Page 5: ...oating P N specify from Table D Recessed Escutcheon Specify Style 50 Recessed Escutch eon with specify finish P N specify Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify W Type 6 Sprinkler Wrench P N 56 000 6 387 Specify W Type 7 Recessed Sprinkler Wrench P N 56 850 4 001 SPRINKLER FINISH 1 NATURAL BRASS 3 PURE WHITE RAL9010 1 POLYESTER 4 SIGNAL WHITE RAL9003 POLYESTER 9 CHROME PLATE...

Page 6: ...re Protection Association TEFLON is a registered trademark of DuPont 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2018 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice ...

Reviews: