Damocles2
Damocles2
Damocles2
42
43
GSM SMS interface
Configures the parameters for sending text messages.
•
GSM Function
– Selects whether SMS are sent through a local modem (only available if the
serial port is in GSM Modem mode).
•
SMS+Ring when Alarm
– Enables sending a SMS and then dialing the number.
•
RS-232 GSM module
(only for Damocles2 2404 with a RS-232 modem connected) – Indicates if
the GSM modem is ready.
•
Not Enabled
– Modem inactive. Shown after changing RS-232 port configuration but before
saving it.
•
Not Found
– Damocles2 is configured for a locally-connected GSM modem but the modem
was not found.
•
Waiting for modem
– Looking for the modem.
•
Initializing
– The modem is being initialized.
•
Ready
– The modem is ready.
•
SMS center Number
(only for Damocles2 2404 with a RS-232 modem connected) – Provider’s
SMS center number, as read from the SIM card. If the number has not been read, it is not
possible to send SMS.
Sekce GSM SMS recipients
Configures the numbers of SMS recipients, regardless of the mode of operation (local/remote
modem).
•
Send test SMS
– Send a test SMS to all configured numbers.
•
RingOut Test
– Dials all configured numbers.
Tip:
For detailed description of the SMS format, see the SMS interface description in the “Using Damoc-
les2 units in your programs” section.
http://hw-group.us/cs/podpora/kba004-pouziti-damocles2-ve-vasich-programech
.
Note:
Any changes must be confirmed by clicking the Apply Changes button. A successful change is
indicated by an animation in the status bar next to the Apply changes button.
GSM modem (local or remote)
Text messages (SMS) can be sent in two ways:
A) Remote GSM modem
– Damocles2 does not have its own GSM modem. “Serial Port Settings”
is set to “Disabled”. To send a SMS, a GSM modem connected to another Damocles2 unit or
the “HWg-SMS GWx” product is used. The remote GSM modem must be accessible over the
network, via an A address, by default at port 80 under “service.xml”.
B)
Local GSM modem
(only for Damocles2 2404 with a RS-232 modem connected) – A GSM mo-
dem is connected to the RS-232 interface of Damocles2. The modem is powered from its
own adapter or from the 12V terminals. An activated SIM is inserted in the modem, PIN is
disabled. SMS Center should be retrieved from the SIM after start-up.
SOAP protocol is used for communication. If the connection is not established or is refused,
Damocles2 tries to send the SMS again.
The throughput of the remote GSM modem is limited to 5 SMS per minute for Damocles2 units
and about 20 SMS per minute for “SMS GW”.
• Device name:
Damocles2 2404
• Inputs/outputs in alarm:
• Binary 10 = input name
• ON = alarm state, OFF = idle state
SMS example:
Alarm ACTIVATED, Damocles2 2404, Binary 10, ON
Web interface
Web interface
Summary of Contents for Damocles2 1208
Page 1: ...Damocles2 User manual...