SPS Terminals

The SPS terminals 2 and 3 wire to the ZPA-SPS Static Pressure sensor. The sensor should be 
installed on a flat surface so that the diaphragm is in the vertical position. Use the 1/4” x 36” tubing 
provided and connect one end to the (P1+) high pressure fitting on the sensor. The other end of the 
tubing should be connected to the plastic sensing probe mounted in the main discharge air plenum 
prior to any zone dampers or duct transitions. The sensing probe is 2-1/8” x 1/4” O.D. Install and 
mount the probe with the arrow in the direction of airflow. The pressure sensor is factory set for 0.35” 
W.C. but is fully adjustable from 0.08 to 1.2” W.C. The terminals are not polarity sensitive. Use 18-2 
thermostat wire. After removing the outer jacket, strip approximately 1/8” insulation off of each wire. 
Land the wires to terminals 2 and 3 on the pressure sensor and repeat the process on the other end 
by landing the wires to the SPS terminals on thepanel. 

NOTE: The ESP function only works with 3-wire, power open / power close dampers.

3

2

FACTORY SET

 

 0.35” W.C.

AT

STATIC PRESSURE

 

 

SETPOINT DIAL

ZPA-SPS

How ESP Works

As zone dampers open and close, the ZPA-SPS Static Pressure Sensor continuously monitors the 
system static pressure. If the static pressure goes above the static pressure setpoint, the sensor will 
send a signal to the panel which will begin to open selected non-calling zone dampers until the static 
pressure setpoint is maintained. The SPS LED will come on until the static pressure reaches setpoint 
and then will turn off. Any zone with the bypass jumper in the OFF position will not be allowed to 
bleed air.  The small amount of air allowed to bleed into selected non-calling zones eliminates air 
noise and ensures proper airflow through the HVAC system. This also prevents coil freeze up and 
high temperature issues. When all zones are satisfied, all zone dampers will go to the full open 
position provided no thermostat is calling for ventilation mode. 

CONTROL MUST BE MOUNTED

IN VERTICAL POSITION

THE 1/4” TUBING SHOULD BE

CONNECTED TO P1+ 

HIGH PRESSURE FITTING ON THE

PRESSURE SENSOR

AIR HANDLER

RETURN

AIR

SUPPLY

AIR

INSTALL

SENSING

PROBE

WITH ARROW

IN DIRECTION

OF AIRFLOW

ZPA-SPS

Summary of Contents for ZP4-ESP

Page 1: ...Indianapolis IN 46237...

Page 2: ...SPS Terminals 7 How ESP Works 7 Zone Thermostats 8 Single Stage Heat Cool 8 Multi Stage Heat Cool 8 2 Heat 1 Cool Heat Pump or Fossil Fuel 8 3 Heat 2 Cool Heat Pump or Fossil Fuel 9 Zone Dampers 9 Pa...

Page 3: ...will come on with the non calling zone LEDs until the static pressure reaches setpoint The small amount of air allowed to bleed into non calling zones eliminates air noise and assures proper air ow t...

Page 4: ...3 PANEL POWER LED 14 ZONE 1 LED 15 ZONE 2 LED 16 ZONE 3 LED 17 ZONE 4 LED 18 ESP LED 19 HIGH LIMIT POTENTIOMETER 20 LOW LIMIT POTENTIOMETER 21 DISCHARGE AIR SENSOR LED 22 HIGH BALANCE POINT POTENTIOME...

Page 5: ...ow voltage cable must be 18 gauge solid not stranded wire 4 All wiring should be color coded and tagged for proper identi cation Mounting the Panel Carefully remove the panel from the shipping carton...

Page 6: ...r cooling coil and upstream of any duct transitions or zone dampers Wire the sensor to the S and DA DAS terminals on the panel The sensor is used for High and Low Limit protection ZPA DTS Outdoor Temp...

Page 7: ...e power open power close dampers 3 2 FACTORY SET 0 35 W C AT STATIC PRESSURE SETPOINT DIAL ZPA SPS How ESP Works As zone dampers open and close the ZPA SPS Static Pressure Sensor continuously monitors...

Page 8: ...The Panel has inputs for four zone thermostats Each zone thermostat must be equipment compatible C R Y1 Y2 G W1 AUX W2 OB C R Y1 W1 G C R Y1 Y2 G W1 AUX W2 OB C R Y1 Y2 W1 W2 G C R Y1 Y2 G W1 AUX W2 O...

Page 9: ...wire oating point actuators rated at 2 5VA NOTE 3 wire dampers must be used with the ESP function that eliminates the need for a traditional bypass damper FP MOTOR 18 24 VAC DC 2 5 1 5W VA 1 Comm 2 Cl...

Page 10: ...SW 6 Capacity Control option Right No Capacity Control Left Only allow additional equipment staging if 2 or more zones are calling and at least one zone is calling for an additional stage LIMIT ADJUS...

Page 11: ...Red Red Red Red Red Red Red Power Static Pressure Control Zone Damper 1 Zone Damper 2 Zone Damper 3 Zone Damper 4 Discharge Air Sensor Outdoor Temp Sensor Speed Up Mode 1st Stage Compressor 2nd Stage...

Page 12: ...tat in the continuous fan ON mode The following LEDs should be lit PWR ZD1 DAS If Discharge Air Sensor is wired to panel OTS If Outdoor Temperature Sensor is wired to panel G 9 Put zone 1 thermostat i...

Page 13: ...is wired to panel W1 W2 If two stage system and setpoint is high enough to energize second stage G If fan selector switch is set for electric Conventional Heat Pump or Fossil Fuel PWR ZD1 DAS If Disc...

Page 14: ...gle or multi stage Programmable or non programmable Auto or manual changeover Sensors ZPA DTS Discharge Temperature Sensor NTC Type 3 10K 77 F 3 77 F ZPA OTS Outdoor Temperature Sensor NTC Type 3 10K...

Reviews: