BALANCE POINT ADJUSTMENTS:
When used with a heat pump or dual fuel system and fitted with a
ZPA-OTS outdoor sensor, the panel can provide both high and low
balance point control.
High Balance Point -
The panel has a potentiometer marked HI BAL
PT that is adjustable from 20° to 60° F. If the outdoor temperature
rises above the high balance point setting, the panel will prevent
auxiliary heat from coming on.
Note:
If a zone thermostat is set in the emergency heat mode, the
panel will override the high balance point setting regardless of the
outdoor temperature and the system will function in emergency heat
until the thermostat is taken out of the emergency heat mode.
Low Balance Point -
The panel has a potentiometer marked LO BAL
PT that is adjustable from 0° - 40° F. If the outdoor temperature falls
below the low balance point setting, the panel will lock out
mechanical heating and change over to the auxiliary heat source.
ZONE BYPASS
Each zone has a Zone Bypass jumper that can be used to remove
the ESP function for that zone. This can be useful in applications
where one zone out of three or four zones may represent a very small
percentage of the total system CFM.
PANEL LED DEFINITIONS AND FUNCTIONS
LED COLOR DEFINITION FUNCTION
PWR
ESP
ZD1
ZD2
ZD3
ZD4
DAS
OTS
SPD
UP
Y1
Y2
W1/AUX
W2/OB
G
Red
Red
Green
Green
Green
Green
Red
Red
Red
Red
Red
Red
Red
Red
Power
Static Pressure
Control
Zone Damper 1
Zone Damper 2
Zone Damper 3
Zone Damper 4
Discharge Air
Sensor
Outdoor Temp
Sensor
Speed Up Mode
1st Stage
Compressor
2nd Stage
Compressor
1st Stage Heat
or Aux Heat
2nd Stage Heat-
Reversing Valve
Fan
ON
- 24VAC to panel
OFF
- No 24VAC to C and R terminals or 3 AMP POWER fuse is blown
ON
- When system static pressure is above static pressure control setpoint
OFF
- When system static pressure is below static pressure control setpoint
ON
- Damper driving open or in the open position
OFF
- Damper in the closed position
BLINKING
- Damper in floating position to relieve static pressure as part of
ESP function
ON
- Confirms discharge air sensor is wired to panel
OFF
- No discharge air sensor wired to panel or wiring problem
BLINKING
- Panel out on High or Low Limit
ON
- Confirms outdoor temperature sensor is wired to panel
OFF
- No outdoor temperature sensor wired to panel or wiring problem
BLINKING
- Panel out on High or Low Balance Point
OFF
- Panel time delays in standard operating mode
BLINKING
- Panel time delays in speed up mode
ON
- Panel calling for 1st stage compressor
OFF
- No call for 1st stage compressor
ON
- Panel calling for 2nd stage compressor
OFF
- No call for 2nd stage compressor
ON
- Panel calling for 1st stage or auxiliary heat
OFF
- No call for 1st stage or auxiliary heat
ON
- Panel calling for 2nd stage heat or reversing valve is energized
OFF
- No call for 2nd stage heat or reversing valve is de-energized
ON
- Fan relay energized
OFF
- Fan relay de-energized