Hvac ZP4-ESP Installation Manual Download Page 3

The ZP4-ESP is a 4 zone universal zone control panel that includes integrated ESP static pressure 
control logic designed to eliminate the need for a conventional bypass damper when used with 3-wire 
zone dampers. The panel is capable of handling up to 2 stages of conventional heating and cooling or 
3 stages of heating and 2 stages of cooling for heat pump and fossil fuel applications. 

SEQUENCE OF OPERATION

 

 

The panel allows a single HVAC unit to have up to four separate zones. Each zone is controlled by its 
own thermostat. When a zone thermostat calls for heating or cooling, the zones not calling will have 
their dampers powered closed, and the zones calling will have their dampers powered opened. The 
heating or cooling equipment will also be brought on. 

As zone dampers open and close, the ZPA-SPS Static Pressure Sensor continuously monitors the 
system static pressure. If the static pressure goes above the static pressure setpoint, the panel will 
send a signal to all selected non-calling zone dampers to start to open to a point where the static 
pressure setpoint is maintained. The ESP LED will come on with the non-calling zone LEDs until the 
static pressure reaches setpoint. The small amount of air allowed to bleed into non-calling zones 
eliminates air noise and assures proper airflow through the HVAC system. This also prevents coil 
freeze up and high temperature issues. 

DESIGN AND INSTALLATION GUIDLINES

 

 

 

[ ] Zone control begins with good 

 design. 

HVAC

[ ] Proper load calculations used to determine duct and equipment sizing are essential in achieving
    optimum performance.

[ ] Install zone thermostats in their respective zones.

[ ] System wires should be tagged to match the panel terminal designations and zone

    identification.

[ ] Zone dampers should be installed at least 10’ back from discharge air grills whenever possible.

[ ] Zone dampers need to be located where they can be accessed for trouble shooting.

[ ] Flex or lined duct is recommended on the last 5’ of each branch run.

[ ] Thermostats and zone dampers can typically be located up to 300’ from the control panel when
    18

 copper thermostat wire is used. 

AWG

[ ] Always use a separate 24

 transformer rated at the proper 

 to power the panel, zone

VAC

VA

    dampers and thermostats.

[ ] Never use the equipment transformer regardless of its 

 rating.

VA

[ ] When using forced air zoning with a variable speed 

 system, high speed fan should be set

HVAC

    at 400 

 per ton of cooling.

CFM

Summary of Contents for ZP4-ESP

Page 1: ...Indianapolis IN 46237...

Page 2: ...SPS Terminals 7 How ESP Works 7 Zone Thermostats 8 Single Stage Heat Cool 8 Multi Stage Heat Cool 8 2 Heat 1 Cool Heat Pump or Fossil Fuel 8 3 Heat 2 Cool Heat Pump or Fossil Fuel 9 Zone Dampers 9 Pa...

Page 3: ...will come on with the non calling zone LEDs until the static pressure reaches setpoint The small amount of air allowed to bleed into non calling zones eliminates air noise and assures proper air ow t...

Page 4: ...3 PANEL POWER LED 14 ZONE 1 LED 15 ZONE 2 LED 16 ZONE 3 LED 17 ZONE 4 LED 18 ESP LED 19 HIGH LIMIT POTENTIOMETER 20 LOW LIMIT POTENTIOMETER 21 DISCHARGE AIR SENSOR LED 22 HIGH BALANCE POINT POTENTIOME...

Page 5: ...ow voltage cable must be 18 gauge solid not stranded wire 4 All wiring should be color coded and tagged for proper identi cation Mounting the Panel Carefully remove the panel from the shipping carton...

Page 6: ...r cooling coil and upstream of any duct transitions or zone dampers Wire the sensor to the S and DA DAS terminals on the panel The sensor is used for High and Low Limit protection ZPA DTS Outdoor Temp...

Page 7: ...e power open power close dampers 3 2 FACTORY SET 0 35 W C AT STATIC PRESSURE SETPOINT DIAL ZPA SPS How ESP Works As zone dampers open and close the ZPA SPS Static Pressure Sensor continuously monitors...

Page 8: ...The Panel has inputs for four zone thermostats Each zone thermostat must be equipment compatible C R Y1 Y2 G W1 AUX W2 OB C R Y1 W1 G C R Y1 Y2 G W1 AUX W2 OB C R Y1 Y2 W1 W2 G C R Y1 Y2 G W1 AUX W2 O...

Page 9: ...wire oating point actuators rated at 2 5VA NOTE 3 wire dampers must be used with the ESP function that eliminates the need for a traditional bypass damper FP MOTOR 18 24 VAC DC 2 5 1 5W VA 1 Comm 2 Cl...

Page 10: ...SW 6 Capacity Control option Right No Capacity Control Left Only allow additional equipment staging if 2 or more zones are calling and at least one zone is calling for an additional stage LIMIT ADJUS...

Page 11: ...Red Red Red Red Red Red Red Power Static Pressure Control Zone Damper 1 Zone Damper 2 Zone Damper 3 Zone Damper 4 Discharge Air Sensor Outdoor Temp Sensor Speed Up Mode 1st Stage Compressor 2nd Stage...

Page 12: ...tat in the continuous fan ON mode The following LEDs should be lit PWR ZD1 DAS If Discharge Air Sensor is wired to panel OTS If Outdoor Temperature Sensor is wired to panel G 9 Put zone 1 thermostat i...

Page 13: ...is wired to panel W1 W2 If two stage system and setpoint is high enough to energize second stage G If fan selector switch is set for electric Conventional Heat Pump or Fossil Fuel PWR ZD1 DAS If Disc...

Page 14: ...gle or multi stage Programmable or non programmable Auto or manual changeover Sensors ZPA DTS Discharge Temperature Sensor NTC Type 3 10K 77 F 3 77 F ZPA OTS Outdoor Temperature Sensor NTC Type 3 10K...

Reviews: