Hvac ZP4-ESP Installation Manual Download Page 14

Indianapolis, IN 46237

www.iohvaccontrols.com

For Technical Support Call Toll Free: 866-225-5032

ZP4-ESP SPECIFICATIONS:

Enclosure:

Aluminum

Panel Dimensions:

Height:  8.75”
Width:  7.0”
Depth  1.5”

PC Board Mounting:

Individual Snap Track mounted to enclosure base

Operating Temperature Rating:

-40° F to 150° F

Operating Humidity:

5% to 90% RH non-condensing

Wiring:

18-gauge wire for all equipment and component  
connections.

Time Delays:

5 minutes off between heating and cooling calls.
3 minutes off on high or low limit
20 minute time share
Purge ON = 1 minute

Thermostats:

Single or multi-stage 
Programmable or non-programmable
Auto or manual changeover

Sensors:

ZPA-DTS Discharge Temperature Sensor
  NTC Type 3, 10K  @ 77° F, +/- 3% @ 77° F

ZPA-OTS Outdoor Temperature Sensor
  NTC Type 3, 10K  @ 77° F, +/- 3% @ 77° F

24. When the system static pressure falls below the ESP static pressure sensor setting, the ESP LED 

will go out but the non-calling zone LEDs will blink confirming they are in a floating position.
25. After confirming the ESP function is working, place the zone one thermostat in the Auto fan mode.
26. The system fan should shut off and all zone LEDs will light confirming that the zone dampers are 

now in the full open position.
27. Place the zone thermostats in their normal operating mode and adjust setpoints and scheduling 
accordingly.

iO-06-1338-090320

Summary of Contents for ZP4-ESP

Page 1: ...Indianapolis IN 46237...

Page 2: ...SPS Terminals 7 How ESP Works 7 Zone Thermostats 8 Single Stage Heat Cool 8 Multi Stage Heat Cool 8 2 Heat 1 Cool Heat Pump or Fossil Fuel 8 3 Heat 2 Cool Heat Pump or Fossil Fuel 9 Zone Dampers 9 Pa...

Page 3: ...will come on with the non calling zone LEDs until the static pressure reaches setpoint The small amount of air allowed to bleed into non calling zones eliminates air noise and assures proper air ow t...

Page 4: ...3 PANEL POWER LED 14 ZONE 1 LED 15 ZONE 2 LED 16 ZONE 3 LED 17 ZONE 4 LED 18 ESP LED 19 HIGH LIMIT POTENTIOMETER 20 LOW LIMIT POTENTIOMETER 21 DISCHARGE AIR SENSOR LED 22 HIGH BALANCE POINT POTENTIOME...

Page 5: ...ow voltage cable must be 18 gauge solid not stranded wire 4 All wiring should be color coded and tagged for proper identi cation Mounting the Panel Carefully remove the panel from the shipping carton...

Page 6: ...r cooling coil and upstream of any duct transitions or zone dampers Wire the sensor to the S and DA DAS terminals on the panel The sensor is used for High and Low Limit protection ZPA DTS Outdoor Temp...

Page 7: ...e power open power close dampers 3 2 FACTORY SET 0 35 W C AT STATIC PRESSURE SETPOINT DIAL ZPA SPS How ESP Works As zone dampers open and close the ZPA SPS Static Pressure Sensor continuously monitors...

Page 8: ...The Panel has inputs for four zone thermostats Each zone thermostat must be equipment compatible C R Y1 Y2 G W1 AUX W2 OB C R Y1 W1 G C R Y1 Y2 G W1 AUX W2 OB C R Y1 Y2 W1 W2 G C R Y1 Y2 G W1 AUX W2 O...

Page 9: ...wire oating point actuators rated at 2 5VA NOTE 3 wire dampers must be used with the ESP function that eliminates the need for a traditional bypass damper FP MOTOR 18 24 VAC DC 2 5 1 5W VA 1 Comm 2 Cl...

Page 10: ...SW 6 Capacity Control option Right No Capacity Control Left Only allow additional equipment staging if 2 or more zones are calling and at least one zone is calling for an additional stage LIMIT ADJUS...

Page 11: ...Red Red Red Red Red Red Red Power Static Pressure Control Zone Damper 1 Zone Damper 2 Zone Damper 3 Zone Damper 4 Discharge Air Sensor Outdoor Temp Sensor Speed Up Mode 1st Stage Compressor 2nd Stage...

Page 12: ...tat in the continuous fan ON mode The following LEDs should be lit PWR ZD1 DAS If Discharge Air Sensor is wired to panel OTS If Outdoor Temperature Sensor is wired to panel G 9 Put zone 1 thermostat i...

Page 13: ...is wired to panel W1 W2 If two stage system and setpoint is high enough to energize second stage G If fan selector switch is set for electric Conventional Heat Pump or Fossil Fuel PWR ZD1 DAS If Disc...

Page 14: ...gle or multi stage Programmable or non programmable Auto or manual changeover Sensors ZPA DTS Discharge Temperature Sensor NTC Type 3 10K 77 F 3 77 F ZPA OTS Outdoor Temperature Sensor NTC Type 3 10K...