background image

- 5 - 

Table 5 Overcurrent protection characteristics of circuit breakers for motors 

Rated current In 

(A) 

Thermal release (ambient tempe40°C) 

Operating 

current of 

electromagneti

c release (A) 

[Note] 

1.0 In non-

operating time 

(h) (initial state: 

cold state) 

1.2 In operating 

time (h) (initial 

state: thermal 

state) 

1.5 In operating 

time (min) (initial 

state: thermal 

state) 

7.2 In operating 

time (s) (initial 

state: cold state) 

In≤63

 

>2 

≤2

 

≤2

 

2<Tp≤10

 

(12±2.4)In 

63<In≤250

 

4<Tp≤10

 

250<In≤800

 

≤8

 

6<Tp≤20

 

[Note]: The operating current of the electromagnetic release of HUM8-

630 and 800 (400 A ≤ In ≤ 800 

A) is (5±1) In to 14 In. 

Adjustable reference value: Low (4 – 6) In; Relatively low (6 – 8.3) In; Relatively high (8.3 – 10.9) In; 

High (10.9

–14) In. 

6  Circuit Breaker Accessories  

6.1  List of accessory models (see Table 6). 

Table 6 List of accessory models 

Shell frame level rated current Inm 

(A) 

63 

100 

250 

400 

630, 800 

Internal 

accessories 

Alarm contact 

B1 

B2 

B3 

B4 

Auxiliary contact 

F1 

F2 

F3 

F4 

Shunt trip 

FL1 

FL2 

FL3 

FL4 

Undervoltage release 

QY1 

QY2 

QY3 

QY4 

Accessory terminal 

JX 

External 

accessories 

Rotation operating handle 

CS1-63 

CS1-100 

CS1-250 

CS1-400 

CS1-630 

Electric operating mechanism 

MDX0 

MDX1 

MDX2 

MDX3 

MDX4 

Mechanical interlock 

3-pole 

N1-3 

N2-3 

N3-3 

N4-3 

N5-3 

4-pole 

—— 

N2-4 

N3-4 

N4-4 

N5-4 

6.2  Rated values of auxiliary contacts and alarm contacts 

Conventional thermal current Ith = 6 A; 

Rated working current Ie = 0.79 A (230 V, AC); Ie = 0.47 A (400 V, AC); Ie = 0.15 A 

(220 V, DC). 

6.3  Shunt trip parameters 

Rated voltage Us: AC: 110 V, 230 V, 400 V; input capacity: 180 VA; 

                              DC: 24 V, 48 V, 110 V; input capacity: 60 W. 

The circuit breaker can interrupt reliably under (70%–110%) Us, and the operating 

time is 10 ms–30 ms. 

When the rated control power supply voltage of the shunt trip is DC 24 V, the maximum 

length of the copper conductor shall meet the requirements of Table 7. 

Table 7  Maximum Length of the copper conductor 

Conductor 

Rated control 

area power supply  

voltage Uc (DC 24 V) 

1.5mm

2

 

2.5mm

2

 

100% Uc 

150m 

250m 

80% Uc 

100m 

160m 

If the requirements of the above table are not met, it is recommended to 

design the control circuit of the shunt trip according to Figure 1. 

 

 

Inside the dotted line 

box is the schematic 

diagram of the shunt 

trip 

Power supply input 

The voltage of the input terminal of the power 

supply is: AC 50 Hz 230 V, 400 V 

KA: DC 24 V. The current capacity of the 

intermediate relay contact is 1 A. 

Summary of Contents for HUM8 Series

Page 1: ...please read the instruction carefully and well keep it for future reference Product Certificate This product has passed the inspection and meets the requirements of GB T14048 2 and therefore is allowe...

Page 2: ...Code Y with the special release with prepaid kilowatt hour meter Application code No code for power distribution Code 2 for motor protection Internal accessory code see Table 2 Overcurrent release ty...

Page 3: ...3 The relative air humidity shall not exceed 50 at the maximum temperature of 40 C A higher relative humidity is allowed at a lower temperature The average minimum temperature of the wettest month sh...

Page 4: ...3 4 3 3 4 3 4 3 4 3 Rated insulation voltage Ui V AC 800 AC 1 000 AC 1 000 Flashover distance mm 50 0 50 0 50 0 Rated ultimate service short circuit breaking capacity Ics kA 690V 5 3 10 5 10 5 5 3 10...

Page 5: ...100 100 150 100 200 200 85 85 100 100 150 100 200 200 85 85 100 100 150 100 200 200 Operation performance times Energizing 7500 7500 7500 De energizing 10000 10000 10000 Outline dimensions mm a 140 18...

Page 6: ...dle CS1 63 CS1 100 CS1 250 CS1 400 CS1 630 Electric operating mechanism MDX0 MDX1 MDX2 MDX3 MDX4 Mechanical interlock 3 pole N1 3 N2 3 N3 3 N4 3 N5 3 4 pole N2 4 N3 4 N4 4 N5 4 6 2 Rated values of aux...

Page 7: ...m of the electric operating mechanism Figure 2 Wiring diagram of the MDX Electric Operating Mechanism 6 6 Special release with prepaid kilowatt hour meter The rated working voltage Ue of the special r...

Page 8: ...our company according to the order requirements and cannot be adjusted freely during use 7 4 The handle of the circuit breaker can be in three positions Closed Open and Tripped When the handle is in...

Reviews: