Table 5 Overcurrent protection characteristics of circuit breakers for motors
Rated current In
(A)
Thermal release (ambient tempe40°C)
Operating
current of
electromagneti
c release (A)
[Note]
1.0 In non-
operating time
(h) (initial state:
cold state)
1.2 In operating
time (h) (initial
state: thermal
state)
1.5 In operating
time (min) (initial
state: thermal
state)
7.2 In operating
time (s) (initial
state: cold state)
In≤63
>2
≤2
≤2
2<Tp≤10
(12±2.4)In
63<In≤250
≤
4
4<Tp≤10
250<In≤800
≤8
6<Tp≤20
[Note]: The operating current of the electromagnetic release of HUM8-
630 and 800 (400 A ≤ In ≤ 800
A) is (5±1) In to 14 In.
Adjustable reference value: Low (4 – 6) In; Relatively low (6 – 8.3) In; Relatively high (8.3 – 10.9) In;
High (10.9
–
–14) In.
6 Circuit Breaker Accessories
6.1 List of accessory models (see Table 6).
Table 6 List of accessory models
Shell frame level rated current Inm
(A)
63
100
250
400
630, 800
Internal
accessories
Alarm contact
B1
B2
B3
B4
Auxiliary contact
F1
F2
F3
F4
Shunt trip
FL1
FL2
FL3
FL4
Undervoltage release
QY1
QY2
QY3
QY4
Accessory terminal
JX
External
accessories
Rotation operating handle
CS1-63
CS1-100
CS1-250
CS1-400
CS1-630
Electric operating mechanism
MDX0
MDX1
MDX2
MDX3
MDX4
Mechanical interlock
3-pole
N1-3
N2-3
N3-3
N4-3
N5-3
4-pole
——
N2-4
N3-4
N4-4
N5-4
6.2 Rated values of auxiliary contacts and alarm contacts
Conventional thermal current Ith = 6 A;
Rated working current Ie = 0.79 A (230 V, AC); Ie = 0.47 A (400 V, AC); Ie = 0.15 A
(220 V, DC).
6.3 Shunt trip parameters
Rated voltage Us: AC: 110 V, 230 V, 400 V; input capacity: 180 VA;
DC: 24 V, 48 V, 110 V; input capacity: 60 W.
The circuit breaker can interrupt reliably under (70%–110%) Us, and the operating
time is 10 ms–30 ms.
When the rated control power supply voltage of the shunt trip is DC 24 V, the maximum
length of the copper conductor shall meet the requirements of Table 7.
Table 7 Maximum Length of the copper conductor
Conductor
Rated control
area power supply
voltage Uc (DC 24 V)
1.5mm
2
2.5mm
2
100% Uc
150m
250m
80% Uc
100m
160m
If the requirements of the above table are not met, it is recommended to
design the control circuit of the shunt trip according to Figure 1.
Inside the dotted line
box is the schematic
diagram of the shunt
trip
Power supply input
The voltage of the input terminal of the power
supply is: AC 50 Hz 230 V, 400 V
KA: DC 24 V. The current capacity of the
intermediate relay contact is 1 A.