HUYU HUM8 Series Installation And Operation Instruction Manual Download Page 7

- 6 - 

6.4  Parameters of the undervoltage release 

Rated voltage Ue: AC: 110 V, 230 V, 400 V; DC: 24 V, 48 V, 110 V. 

The circuit breaker can interrupt reliably under (35%–70%) Us, and the operating time 

is 10 ms–30 ms. When the power supply voltage is less than 35% Ue, the circuit 

breaker can be prevented from closing. When the power supply voltage is more than 

or equal to 85% Ue, the circuit breaker can be reliably closed. 

6.5  See Table 8 for the parameters of the electric operating mechanism. 

Table 8 Main technical parameters of the MDX Electric Operating Mechanism 

Shell frame level rated current Inm (A) 

63 

100 

250 

400 

630, 800 

Model of electric operating mechanism 

MDX0 

MDX1 

MDX2 

MDX3 

MDX4 

Rated working voltage Ue (V) 

AC 110V–230V, 50Hz; DC 110V–220V 

Starting current (A) 

0.5 

Operating time (s) 

≤0.8

 

Rated operating frequency (times/h)) 

180 

120 

Mechanical life (times) 

15,000 

9,000 

5,000 

3,000 

The power supply capacity of the electric operating mechanism shall be large enough to ensure that the 

voltage applied to the electric operating mechanism under the starting current is not less than 85% Ue. 

See Figure 2 for the wiring diagram of the electric operating mechanism. 

 

Figure 2 Wiring diagram of the MDX Electric Operating Mechanism 

6.6  Special release with prepaid kilowatt-hour meter 

The rated working voltage Ue of the special release with prepaid kilowatt-hour meter 

is AC 240 V/50 Hz. It can work normally in the range of (65%–110%) Ue. When the 

Ctrl terminal is cut off, the breaker will delay opening by 0.5 s–2 s. See Figure 3 for 

the wiring diagram. 

 

6.7  Parameters of the overvoltage release (applicable to 4-pole circuit breaker): 

Rated working phase voltage Ue: AC 230 V 50 Hz (or 60 Hz). 

Release operation characteristics: When the main circuit phase voltage is (85%–

110%) Ue, the release shall be able to keep the circuit breaker working for a long 

time. When the phase voltage of the main circuit rises to 270 (1±5%) V, the release 

combined with the circuit breaker shall operate to open the circuit breaker. See Figure 

4 for the wiring diagram. 

 

Figure 4 Wiring diagram of the overvoltage release 

MDX 

type

 

Closed

 

Open

 

R

el

ea

se

 

Circuit breaker 

L1-N 

Rated working voltage Ue of 

Ctrl-N: AC 240 V/50 Hz 

Note: N is connected to 

the power neutral wire, 

and Ctrl is connected to 

the control signal terminal 

of the prepaid kilowatt-

hour meter.

 

R

el

ea

se

 

P1, P2, UC1 and UC2 

on the 

release

 must correspond to 2, 4, 6 

and N on the load side of the access 

circuit breaker. 

Summary of Contents for HUM8 Series

Page 1: ...please read the instruction carefully and well keep it for future reference Product Certificate This product has passed the inspection and meets the requirements of GB T14048 2 and therefore is allowe...

Page 2: ...Code Y with the special release with prepaid kilowatt hour meter Application code No code for power distribution Code 2 for motor protection Internal accessory code see Table 2 Overcurrent release ty...

Page 3: ...3 The relative air humidity shall not exceed 50 at the maximum temperature of 40 C A higher relative humidity is allowed at a lower temperature The average minimum temperature of the wettest month sh...

Page 4: ...3 4 3 3 4 3 4 3 4 3 Rated insulation voltage Ui V AC 800 AC 1 000 AC 1 000 Flashover distance mm 50 0 50 0 50 0 Rated ultimate service short circuit breaking capacity Ics kA 690V 5 3 10 5 10 5 5 3 10...

Page 5: ...100 100 150 100 200 200 85 85 100 100 150 100 200 200 85 85 100 100 150 100 200 200 Operation performance times Energizing 7500 7500 7500 De energizing 10000 10000 10000 Outline dimensions mm a 140 18...

Page 6: ...dle CS1 63 CS1 100 CS1 250 CS1 400 CS1 630 Electric operating mechanism MDX0 MDX1 MDX2 MDX3 MDX4 Mechanical interlock 3 pole N1 3 N2 3 N3 3 N4 3 N5 3 4 pole N2 4 N3 4 N4 4 N5 4 6 2 Rated values of aux...

Page 7: ...m of the electric operating mechanism Figure 2 Wiring diagram of the MDX Electric Operating Mechanism 6 6 Special release with prepaid kilowatt hour meter The rated working voltage Ue of the special r...

Page 8: ...our company according to the order requirements and cannot be adjusted freely during use 7 4 The handle of the circuit breaker can be in three positions Closed Open and Tripped When the handle is in...

Reviews: