SPLIT CONDENSERS
September 1, 1997
P/N 401789
5 - 9
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
To
H/R
From
Turba-Shed
From
H/R
H/R
Valve
To
Cond
To
Suction
O
PTIONAL
F
ACTORY
I
NSTALLED
S
PLIT
C
ONDENSER
V
ALVE
6 Ft Minimum
Recommended
Field-Supplied and
Installed Hand Valves
Recommended
Field Piping
Suction
Drain Line
Condensate
Lines
Suction
Manifold
Oil Separator
Check Valve
Flooding Valve
Comp
3
Comp
2
Comp
1
Header End
of Condenser
Remote Condenser
Receiver
1
2
3
H4
H3
W
P
Split Condenser
Bleed Line
Solenoid
N.C.
Condenser
Solenoid or
3-Way Valve
N.O.
Solenoid
Relay
X2
R
R
R
R
B
B
B
B
P
SR
Condenser
Fan Relay
Ambient
Thermostat
CO 45
°
CI 40
°
1
2
3
X1
High Pressure
Side
BL
1
2
3
Figure 5-5 — Split Condenser Piping Method
Figure 5-6 — Split Condenser Wiring Diagram – Factory and Field Installed Kits
Note: Units with Heat Reclaim should
have the lockout control set to prevent
the heat reclaim from being activated
below the following discharge pressure
values:
R-22 — 135 psig
R-507 — 170 psig
R404a — 165 psig
High Pressure Control Settings
Refrigerant
Cut-Out
Cut In
R-404a
250
195
R22
210
160
R507
260
200