POWER MONITOR
The single phase monitor detects phase loss,
phase reversal, low voltage, and phase imbalance.
It opens the control circuit when any of these con-
ditions occurs. When the fault is corrected, it will
automatically reset. The normally open contacts
will close when 3 Phase voltage is applied to the
three input terminals. The monitor has an indi-
cator that lights as long as it is
not
tripped.
The low voltage cutout is adjustable from 180 to
230 volts for 208/230 volt units, and from 380 to
460 volts for 440 volt units. This should be adjust-
ed to 15% below the nominal line voltage at
power source. A voltmeter should be used to
establish actual supply voltage.
The monitor controls a two pole bypass relay
(BP) making and breaking power to the control
panel.
September 1, 1997
P/N 401789
4 - 29
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
L1
L2
L3
NC
NO
C
380
400
420
440
460
OUTPUT
ON
CONTACTS
7 A, 240VAC
SUPPLY:
440-480V,
3Ø
NC
NO
C
UNDER
VOLTAGE
PVCL —400—AR
0
1
2
4
6
8
Single Phase Monitor
Figure 4-27 Power Monitor and Slave Contactor