LIFTING AND LEVELING
Using rigging with a spreader bar, the Scroll Plus
System may be lifted into position. The spreader
bar is required to prevent damage to the unit.
Note: This unit is front heavy, due to the control
Panel(s), and compressor locations. Take neces-
sary precautions when lifting, and lift only from
lower base support feet.
Vibration isolation pads are supplied with each
rack. The entire weight of the rack must rest on
these pads, with the rack cross leveled. To adjust
for slightly uneven floors, place 16 gauge 3 x 3
galvanized steel shims between the pads and the
floor. (Shims must be field supplied.)
SETTING WITHOUT A CRANE
In many locations crane lifting may not be prac-
tical. Where possible use equipment dollies
centered under each foot, or Johnny Bars. Do
not push or pull on any of the pipes, valves,
accessories, or control panels when moving the
Scroll Plus System.
For mezzanine installations, a fork lift (operated
within its height and weight limits) may be used
to raise the Rack into position.
Caution:
The unit is front heavy due to the
control panel(s), and compressor locations. Take
necessary precautions when lifting, and lift only
from lower base support feet.
September 1, 1997
P/N 401789
1 - 5
HUSSM ANN CORPORATION • BRIDGETON, M O 63044-2483 • Printed in USA
Use Appropriate Spreader Bars
Two 1" Pads
Front and Back
1" Pads Under
Center Support
Two 1" Pads
Front and Back
Figure 1-4 — Lifting and Leveling the Scroll Plus System
Return to Contents