Hudson River Westpoint Operating & Installation Instructions Manual Download Page 9

 

9

OPERATING INSTRUCTIONS

 

 

Control Board Functions

 

T-STAT/Manual Switch:

  This switch selects the pellet stove operating mode.  Slide the 

switch to Manual (the far right position) to be able to manually select the heat settings 
and controls.   
If you have a remote thermostat attached and wish to have the pellet stove controlled by 
the thermostat, slide the switch to T-STAT (the middle position) to operate the pellet 
stove in variable heat mode.  The thermostat will control the heat output of the pellet 
stove alternating between the lowest heat level and the highest heat level pre-selected by 
the user. 
After switching between modes the stove should be turned Off and back On to reset the 
control to operate in that mode. 
 

On/Off Button:

  This button is used to turn the unit on and off.  If the stove is cold prior 

to start-up press and release the On/Off button.  The green light above the On/Off switch 
will flash to indicate start up cycle has started.  Fuel pellets will start to feed into the burn 
pot.  The electric ignition system will be automatically activated, flames in the burn pot 
will normally appear between 3 - 7 minutes.  Once the flame has been established, the 
start up cycle will end, this takes between 10 -15 minutes.  At this point the user will be 
able to make heat level adjustments.   
If the stove is warm at restart the On/Off button must be pressed down and held for 2 
seconds, or more, until the minimum heat level setting light is lit.   
 

Heat Level:

  When pressed this increases the heat level setting one level.  Pressing the 

button will cycle the heat setting from minimum to maximum and back again.  The 
convection fan speed will also increase with the heat level setting.  When the light is 
flashing during the start up cycle the heat level button will not respond to the 
adjustments.  When the light is solid, indicating the start up cycle is finished, it will then 
respond (only in manual mode). 
 

Fan:

  Use this button to override the automatic fan speed control to turn the convection 

fan on high.  The smart control on this pellet stove will vary the fan speed in accordance 
with the heat level setting.  It is recommended to let the controller automatically adjust 
the speed of the fan for optimum efficiency and minimal fan noise. 
 

Auger:

  Pressing and holding this button will turn on the auger to speed feeding of pellets 

into the burn pot, when first using the pellet stove or when you completely empty the 
hopper of pellets and restarting after reloading the hopper.  You can load the auger faster 
by pressing and holding this button (until you see pellets dropping into the burn pot).  
This button will turn off after 1 minute and must be released and pressed again if you 
want to continue to manually operate the auger. 

Summary of Contents for Westpoint

Page 1: ...5639 Please read this entire manual before installation and use of this pellet fuel burning room heater Failure to follow these instructions could result in property damage bodily injury or even deat...

Page 2: ...ons 6 Operating Instructions 7 10 Thermostat Installation 11 Clearances to Combustibles 13 Installing Your Room Heater 12 21 Mobile Home Installations 23 Vent Termination Locations 24 Maintenance 25 2...

Page 3: ...mum Standard grade Moisture Content 8 maximum Heat Content minimum 8 200 btu hr It is important to note that the ash content of the fuel and frequency of operation determine the frequency of cleaning...

Page 4: ...to an outside combustion air source It is recommended that the exhaust vent be cleaned bi annually or after every two tons of pellets Soot or creosote may accumulate when the stove is operated under i...

Page 5: ...use outdoor air for combustion Always install a manufactured fresh air intake kit from outside of the residence See the Installation section for the correct part numbers when ordering these component...

Page 6: ...6 SPECIFICATIONS Heating Specifications Burn Rate 6 5lbs hr on 5 setting 55 000 60 000 Btu s hr Hopper Capacity 130 lbs Depends on quality and heating value of pellet fuel DIMENSIONS Figure 1...

Page 7: ...oard functions and familiarize yourself with how the pellet stove works It is in this mode that the heat level for the AUTO and T STAT mode is set To Start up a Cold Stove Press and release the On Off...

Page 8: ...may do so by pressing the FAN button If the flame goes out or the heat output is too high on minimum heat level setting use the AUGER TRIM button to make adjustments See the AUGER TRIM button descript...

Page 9: ...o make heat level adjustments If the stove is warm at restart the On Off button must be pressed down and held for 2 seconds or more until the minimum heat level setting light is lit Heat Level When pr...

Page 10: ...actory setting and works for most types of fuel Figure 2 Control Panel Open Door If the door is opened while the unit is operating it must be closed within 30 seconds or the unit will go into vacuum e...

Page 11: ...t Disconnect unit from power supply Open right side panel to gain access to rear of control panel Take the thermostat wires and connect to the green screw terminal on the rear of the control panel see...

Page 12: ...cified in NFPA 211 or the applicable building and mechanical codes If factory built the chimney specified shall be listed to the requirements of UL 103 or ULC S629M or if masonry shall meet the constr...

Page 13: ...13 CLEARANCES TO COMBUSTIBLES INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER Figure 4 Figure 5...

Page 14: ...the instructions which come with the wall thimble for this step 9 Install the appropriate length of exhaust vent pipe into the wall thimble See step 11 when determining the correct length of exhaust...

Page 15: ...d horizontal termination cap or if necessary install a 90 elbow and appropriate length of vertical venting A listed vertical vent cap is recommended however if local codes allow when the vent terminat...

Page 16: ...nt joint connections with 3 screws Seal the exhaust vent joint connections with high temperature silicone sealant 4 Install the combustion air intake pipe 5 Install a tee with a cleanout on the exhaus...

Page 17: ...xhaust vent through the wall be sure to make sure that 3 75 mm clearances to combustibles are maintained 9 Secure all vent joint connections with 3 screws Seal the exhaust vent joint connections with...

Page 18: ...18 Figure 9...

Page 19: ...19 SELKIRK DIRECT TEMP VENT SYSTEM FOR PELLET APPLIANCES Images courtesy of Selkirk...

Page 20: ...20 SELKIRK DIRECT TEMP VENT SYSTEM FOR PELLET APPLIANCES Images courtesy of Selkirk UP OUT HORIZONTAL TERMINATION KIT Figure 10...

Page 21: ...21 SELKIRK DIRECT TEMP VENT SYSTEM FOR PELLET APPLIANCES Images courtesy of Selkirk STRAIGHT OUT HORIZONTAL TERMINATION KIT Figure 11...

Page 22: ...22 SELKIRK DIRECT TEMP VENT SYSTEM FOR PELLET APPLIANCES Images courtesy of Selkirk THROUGH THE ROOF VERTICAL TERMINATION KIT Figure 12...

Page 23: ...he holes provided in the pedestal base Ensure that the unit is permanently electrically grounded to the chassis of your home IT IS MANDATORY TO TAKE THE COMBUSTION AIR FROM THE OUTSIDE WHEN INSTALLING...

Page 24: ...F 12 30 cm To outside corner G 12 30 cm To inside corner combustible wall H 3 91 cm within a height of 15 4 5 m above the meter regulator assembly To each side of center line extended above natural g...

Page 25: ...ing the burn pot Inspect the burn pot regularly to check that the holes have not become plugged If necessary clean thoroughly It is imperative that the burn pot be re installed the correct way or the...

Page 26: ...osed of by burial in soil or otherwise locally dispersed they should be retained in the closed container until all cinders have been thoroughly cooled Cleaning Heat Exchanger Tubes Your unit is design...

Page 27: ...ld up continuously it may impede the exhaust flow 3 Inspection of Vent System The chimney venting system should be inspected should be inspected annually or per ton of fuel to determine if creosote or...

Page 28: ...door frame Replace only with ceramic glass obtainable from the dealer Task Maintenance Schedule Burn Pot check daily Combustion Chamber weekly Heat Exchanger Tubes bi weekly Ash Pan bi weekly or every...

Page 29: ...switch trips again contact your local dealer for service Condition 3 Exhaust blower does not operate normally Check all wiring connections Condition 4 Convection blower does not operate normally Check...

Page 30: ...liner then the fire is going out before the unit shuts off On the control panel turn the heat level up to the next setting poorer quality pellets require a slightly higher setting Condition 10 Glass...

Page 31: ...31 WIRING DIAGRAM...

Page 32: ...s well as voiding the Warranty Item Part control panel circuit board SPSW1008 auger motor SPSW1006 250 F normally open high limit snap disc SPSA1016 140 F normally open exhaust temperature snap disc S...

Page 33: ...rized Inca Metal dealer and is subject to the following conditions and limitations This factory warranty is nontransferable and may not be extended whatsoever by any of our representatives A licensed...

Page 34: ...product its components or accessories are excluded Inca Metal neither assumes nor authorizes any third party to assume on its behalf any other liabilities with respect to the sale of this product Inca...

Reviews: