17
FREESTANDING EXTERIOR VERTICAL INSTALLATION
7/.
Locate the center of the exhaust pipe, and air intake connector of your unit. These
points should then be extended to the interior wall of your house. Once you have
located the center point, on the interior wall, cut a hole in the wall as shown in the
instructions for the accompanying wall thimble.
8/.
Install a listed exhaust vent through the wall, be sure to make sure that 3” (75
mm) clearances to combustibles are maintained.
9/.
Secure all vent joint connections with 3 screws. Seal the exhaust vent joint
connections with high temperature silicone sealant.
10/.
Install a Tee with a cleanout on the end of the exhaust pipe, then install listed
venting upward from there. Be sure to install support brackets every 5’ (1500
mm) to keep the venting straight and secure.
11/.
Extend the exhaust vent through the roof flashing and ensure that the vertical cap
is approximately 36” (900 mm) above the roof.