U-ONE
®
-SAFETY Compact
Configuration manual SCU C / SRC C / SGS C
USC42_SCU-KonfigManual-en_R5
23
6.1.3 Current output (non safety related)
The current output can be set to speed or position dependent on the menu and must be
activated before use.
6.1.3.1
Configuring the position-dependent current output
To configure the position-dependent current output it is nec-
essary to enter 2 position values, which must be within the
system limits.
The smaller position value is assigned current I
min
= 4 mA and
the larger position value I
max
= 20 mA.
The following restriction applies:
•
Pos1 < Pos2
If the current position is outside of the defined position range,
the current output is switched to high impedance (I = 0 mA).
(Factory setting).
Alternatively, it is possible to select a setting to take effect in
the event the value falls below or exceeds the determined po-
sition range 4 mA or 20 mA.
6.1.3.2
Configuring the speed-dependent current output
To configure the speed-dependent current output it is neces-
sary to enter the speed
n20 mA
. When at a standstill a current of
4 mA flows.
The following constraint applies:
•
n
20 mA
< (approved mechanical speed -10%)
If the speed exceeds the speed range (n
current
> n
20 mA
), the cur-
rent output is switched to high resistance
(I = 0 mA) – (factory setting).
Alternatively, it is possible to select a setting to take effect in
the event the value exceeds the determined position range
20 mA
.
6.1.4 Configuring the incremental output (non safety-related)
The incremental output is optional. To configure the incre-
mental output it is possible to select a pulse rate of 1024 or
4096
(factory setting: 4096).
Fig. 6-4: Configuring position depend-
ent-current output
Fig. 6-6 Configuring incremental output
Fig. 6-5: Configuring speed dependent-
current output