18
SpikeShield
®
Non-Modular Surge Protective Device (SPD)
OPERATION
Hubbell Wiring Devices
1-800-729-3406 | www.Hubbell-Wiring.com
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Hubbell for any consequences arising out of the use of this material.
Remote Monitor Option
The remote monitor option (Figure 12) has two LEDs, one red and one
green, and an audible alarm with an enable/disable switch. Normal status is
a lit green LED, and no audible alarm. To test the integrity of the remote
monitor, press the push-to-test switch. If the alarm in enabled, the green
LED will turn off, the red LED will turn on, and the alarm will sound.
Releasing the switch will complete the test; the red LED will turn off, the
green LED will turn on and the alarm will shut off.
If suppression on any phase is lost, the green LED will turn off, the red LED
will turn on and an alarm will sound. The audible alarm can be silenced by
pushing the alarm enable/disable button. The alarm will silence and the
green alarm LED will not be lit. The red LED will continue to be illuminated
until the inoperative condition has been cleared.
The remote monitor includes a 120 Vac to 12 Vdc adapter with a six-foot
power cord. Connections are made to the SPD diagnostic panel with
3-position Form “C” type dry contacts (provided) and the appropriate length
of solid or stranded 22 to 14 AWG wire (not provided).
Figure 12:
Remote Monitor Option
= OK
= Fault / Falla / Défaut
Bouton pousser pour vérifier
Monitor Remoto / Moniteur À Distance
[63.5]
2.500
[31.8]
1.25
[88.9]
3.500
[100.3]
3.950
[5.86]
0.230
[5.86]
0.460
[4.75]
2x Ø 0.187
[111.76]
4.400
[3.3]
0.130
[28.58]
1.125
120 Vac power cord
in
[mm]
Dry contacts