Hubbell SPIKESHIELD HBL10P120B Installation Instruction Download Page 10

10

SpikeShield

® 

Non-Modular Surge Protective Device (SPD) 

GROUNDING

 

Hubbell Wiring Devices

 1-800-729-3406 | www.Hubbell-Wiring.com

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. 
No responsibility is assumed by Hubbell for any consequences arising out of the use of this material.

Grounding

The SPD product has leakage current to ground when energized and can 
present a hazardous touch voltage.

The device has SPD components connected from phase to ground. To 
prevent hazardous touch voltage on the SPD enclosure during normal 
operation or during SPD end-of-life, it is critical that there be a robust and 
effective connection to the building grounding structure. The grounding 
connection must utilize an equipment grounding conductor run with the 
phase and neutral (if present) connection of the power system. The SPD 
should not be connected to a separate isolated ground.

When metallic raceway is used as the wiring method, an insulated 
grounding conductor should be run inside the raceway and sized in 
accordance with all applicable codes. Maintain electrical continuity at all 
raceway connections using appropriate bonding devices and do not install 
isolating bushings to interrupt a metallic raceway run.

For best overvoltage suppression by the SPD, use a single-point ground 
system where the service entrance grounding electrode system is 
connected to and bonded to all other available electrodes, building steel, 
metal water pipes, driven rods, etc. (for reference, see IEEE 142-2007). The 
ground impedance measurement of the electrical system should be as low 
as possible, and in compliance with all applicable codes.

SPD rated for use on solidly-grounded power systems must not be 
connected to resistance-grounded (for example HRG) or ungrounded power 
systems. Such a connection can result in damage to the components within 
the SPD product.

WARNING

HAZARDOUS TOUCH VOLTAGE

• Connect the SPD ground terminal to the building grounding grid 

structure.

• Use an appropriately sized equipment grounding conductor.

• When using metallic raceway or conduit:

— Do not use the SPD ground unless augmented with an insulated 

equipment grounding conductor installed inside the metallic raceway or 
conduit.

— Do not use isolated bushings to interrupt the metallic raceway or 

conduit.

— Maintain electrical continuity at all raceway and conduit connections 

using appropriate bonding devices.

• Do not use a separate isolated ground for the SPD.

• Verify proper equipment connection to the grounding system.

• Verify ground grid continuity by performing regularly scheduled 

inspections and testing as part of a comprehensive electrical 
maintenance program.

Failure to follow these instructions can result in death or serious injury.

Summary of Contents for SPIKESHIELD HBL10P120B

Page 1: ...SPIKESHIELD BRANCH PANEL Non Modular Surge Protective Device SPD Installation Instruction Catalog Numbers HBL3P120B HBL4P120B HBL6P120B HBL8P120B HBL10P120B 8222 0507A 06 2010 Retain for future use...

Page 2: ...ce 6 Equipment Performance 6 Electrical 7 Voltage Rating 7 Terminals Wire Size and Installation Torque 8 Branch Circuit Overcurrent Protection and Disconnect Means 8 Integral Switch 9 Location of SPD...

Page 3: ...onal protective equipment PPE and follow safe electrical work practices See NFPA 70E This equipment must only be installed and serviced by qualified electrical personnel Turn off all power supplying t...

Page 4: ...nal Sine Wave Tracking Module SPD Device Per Phase I2t Iapparent Ip Ith HBL_P120B 240 kA2 seconds 21 500 A RMS 48 000 A RMS 260 A CAUTION LOSS OF SURGE SUPPRESSION Do not energize the SPDs until the e...

Page 5: ...iced by qualified electrical personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Repl...

Page 6: ...he location of the installation Mounting The device is designed to be surface or flush mounted Refer to the device submittal drawings or the product catalog for typical mounting dimensions and weight...

Page 7: ...es whether or not the transformer windings are referenced to earth via a grounding conductor The system configuration is not based on how any specific load or equipment is connected to a particular po...

Page 8: ...parate branch circuit or connected to a suitable existing branch circuit When connected to a separate dedicated branch circuit the OCPD setting must be selected to protect the conductors feeding the S...

Page 9: ...absence of voltage is verified maintenance may now be performed inside the SPD enclosure Upon completion of repairs close the door of the unit and turn the handle to the ON I position Location of SPD...

Page 10: ...voltage suppression by the SPD use a single point ground system where the service entrance grounding electrode system is connected to and bonded to all other available electrodes building steel metal...

Page 11: ...h to the surface of sheetrock or firewall construction Optional Integral Switch After making electrical cable connections to the SPD integral switch and prior to energizing the SPD ensure that the lin...

Page 12: ...ent If the SPD is properly installed and functioning the green LED indicators on the display will be lit If you have any questions pertaining to the installation of this device contact Hubbell at 1 80...

Page 13: ...Connections C A B N 8222 0013 05 SPD A N C B C B A OK Replace Sustituir Remplacer NOTE The neutral conductor is not present on 3 wire grounded neutral power systems For these systems bond the neutral...

Page 14: ...or 4 Wire Grounded Wye Installation wIth Integral Switch Figure 8 Three Phase 3 or 4 Wire High Leg Delta Installation with Integral Switch 8222 0013 08 N SPD A N C B OK Replace Sustituir Remplacer NO...

Page 15: ...had been cleared On an SPD module see Figure 9 if the left green LED is not lit it indicates a loss of suppression from line to ground for that phase If the right green LED is not lit it indicates a...

Page 16: ...loss to the diagnostic display panel To reset the surge counter remove all power and press the small switch located inside the unit on the underside of the diagnostic circuit board near the RJ45 conne...

Page 17: ...y use with energy levels in excess of those discussed in this instruction bulletin are not covered by warranty For application questions contact Hubbell at 1 800 729 3406 Care must be taken in install...

Page 18: ...ed LED will turn off the green LED will turn on and the alarm will shut off If suppression on any phase is lost the green LED will turn off the red LED will turn on and an alarm will sound The audible...

Page 19: ...CTRIC SHOCK EXPLOSION OR ARC FLASH Apply appropriate personal protective equipment PPE and follow safe electrical work practices See NFPA 70E This equipment must only be installed and serviced by qual...

Page 20: ...l distributor or refer to the product catalog SpikeShield modules Replacement instructions are included with the replacement parts Diagnostic display panel assemblies Replacement instructions are incl...

Reviews: