3.1.1.3 Installation Clearances
Reserve sufficient space around the cabinet for operation and ventilation:
Reserve a clearance of at least 800 mm from the front of the cabinets for ventilation and
operation.
Reserve a clearance of at least 500 mm from the top of the cabinets for operation.
Reserve a clearance of at least 500 mm from the rear for ventilation. If the UPS will be
operated from the rear, reserve a clearance of at least 800 mm for operations.
3.1.2 Tools and Instruments
Use insulated tools to avoid electric shocks.
Table 3-1
Tools and instruments
Tools and Instruments
Electric forklift
Manual forklift
Step ladder
Rubber mallet
Hammer drill (with
a Φ16 drill bit)
Hand-held electric
drill
Hole saw
Heat gun
Diagonal pliers
Crimping tool
Wire stripper
Electric hydraulic
pliers
Clamp meter
Multimeter
Cable tie
Horizontal level