Battery Maint. screen
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Battery maintenance includes
Forced Equalized Charging
,
Shallow Dis. Test
, and
Capacity
Test
.
Figure 4-37
Battery Maint. screen
Item
Description
Forced Equalized Charging
Forcibly perform equalized charging on batteries.
Shallow Dis. Test
Partially discharge batteries. A shallow discharge test can
be conducted to test the battery loop reliability and short-
time discharge capacity when the batteries have not
discharged for a long time.
Capacity Test
Fully discharge batteries. A deep discharge test is
conducted to obtain the battery discharge performance
data.
USB Operations
You can export
Fault Data
, and perform
Upgrade Software
,
BSP Upgrade
,
Export Config.
,
and
Import Config.
with USB.
Multi-brand
is used to import the brand information of a partner to the corresponding
WebUI.